Extra Menu

© 2026 Notes Gallery v3.3.1

All rights reserved. Designed for AKTU students.

Saved Bookmarks

Home / AKTU 1ST YEAR NOTES / Fundamentals Of Electrical Engineering Unit 1 Notes- AKTU B.Tech 1st Year

Fundamentals Of Electrical Engineering Unit 1 Notes- AKTU B.Tech 1st Year

Electrical Engineering Unit 1 notes for AKTU: charge, current, voltage, Ohm’s law, DC circuits, dividers, KCL, KVL, nodal, mesh and Thevenin theorem & examples.

Read Notes Free ↓
📥 Download PDF at End of Page ↓

University: Dr. A.P.J. Abdul Kalam Technical University, AKTU

Programme: B.Tech First Year, Semester I and Semester II

Course Codes: AEE101A / AEE201A

Branches: Common to All

Unit: I

Unit Name: Basic Electrical Quantities and DC Circuits

Introduction to Basic Electrical Quantities and DC Circuits

Electrical engineering begins with understanding how electric charge moves, how sources transfer energy and how circuit connections determine voltage and current. These ideas are used in electrical machines, electronic systems, power networks, measurement instruments, control systems and everyday electrical equipment.

A DC circuit provides a useful starting point because the steady-state examples use quantities that remain constant with time. The current direction does not alternate, the source values are specified and positive linear resistors relate voltage and current through Ohm’s law. This makes it possible to concentrate on circuit connections, reference directions, energy transfer and systematic solution methods.

The unit begins with charge, current, potential difference, EMF, resistance and conductance. It then develops series and parallel combinations, voltage and current division, electrical power, energy calculations and practical source models. Kirchhoff’s laws provide the foundation for analysing networks that cannot be solved by an immediate resistor combination.

Nodal analysis uses unknown node potentials and Kirchhoff’s Current Law. Mesh analysis uses loop-current variables and Kirchhoff’s Voltage Law. Thevenin’s theorem replaces a linear source network with a simpler two-terminal equivalent when the external load is the main quantity of interest.

The purpose of studying these methods is to calculate the requested quantities while keeping the physical meaning clear. Current is a rate of charge transfer. Voltage is a difference between two potentials. Power is the rate at which energy is transferred. A resistor absorbs energy while charge continues through the circuit.

Reading a Circuit Before Calculating

Begin every solution by identifying the source network, the external load and the terminals mentioned in the question. A diagram can be stretched or redrawn without changing the circuit when all connections are preserved. Marking each complete wire node with one label makes these relationships easier to see.

Record whether the source is ideal or includes a stated internal resistance. This distinction determines whether its terminal voltage changes when load current changes. A fixed ideal voltage source maintains its stated voltage, while a practical series-resistance model develops an internal voltage drop.

Choose references that make the equations easy to audit. A current arrow defines a positive direction for a variable; it does not predict the eventual physical direction. A voltage polarity defines an ordered difference between two points.

Keep both references unchanged during the calculation. Retain a negative result where it appears and explain its meaning after solving. Finally, check conservation of charge, potential changes around a closed path and electrical power balance.

Unit 1 Topic Map

Topic Main Coverage
Basic electrical quantities Charge, current, voltage, EMF, resistance and conductance
Circuit connections Nodes, branches, loops, meshes, opens and shorts
Resistor networks Series, parallel and mixed combinations
Divider rules Unloaded voltage divider, loaded divider and current divider
Power and energy Resistor dissipation, source power, energy and running cost
Practical sources Internal resistance, terminal voltage and load regulation
Kirchhoff’s laws KCL, KVL and reference conventions
Nodal analysis One-node, two-node and current-injection networks
Mesh analysis Shared resistors, two meshes and multiple sources
Thevenin’s theorem Open-circuit voltage, equivalent resistance and load calculations
Measurement Voltmeter loading and ammeter burden resistance
Revision Formula sheet, short answers and long answers

Syllabus Coverage

  • Electric charge and current.
  • Potential difference and EMF.
  • Resistance, resistivity and conductance.
  • Ohm’s law.
  • Series and parallel resistor combinations.
  • Voltage-divider and current-divider rules.
  • DC electrical power and energy.
  • Kirchhoff’s Current Law.
  • Kirchhoff’s Voltage Law.
  • Branch-current references.
  • Simple nodal analysis.
  • Simple mesh analysis.
  • Thevenin’s theorem and load calculations.
  • Basic electrical measurement and circuit checking.

Numerical Conventions

Unless a problem states otherwise, wires and sources are ideal. Positive resistors are linear elements with constant resistance under the assumed operating conditions.

Use the supplied numerical values. Retain useful precision during the working and round the displayed result at the end. A negative answer must be interpreted against the current arrow or voltage polarity originally assigned.

Use the same element’s voltage and current when calculating its power. Do not combine source voltage with a branch current unless those quantities actually belong to the same two-terminal element.

1. Electrical Quantities and the DC Circuit Model

An electrical circuit provides connected paths through which charges can move and energy can be transferred. Sources supply or absorb energy, conductors connect components and loads convert electrical energy into forms such as heat, light or mechanical work.

Direct current means current with a fixed direction. In the steady DC examples considered here, the electrical quantities are constant. The term DC does not by itself mean that every possible waveform must be perfectly constant; the numerical model used in this unit is the steady constant-value model unless another condition is stated.

Source, conducting path and resistive load in a complete DC circuit

Figure 1.1
A source, conducting path and resistive load form a complete circuit. The current arrow gives a chosen conventional direction, while source and resistor polarities define voltage references.
Quantity Symbol SI Unit
Electric charge Q Coulomb, C
Electric current I Ampere, A
Potential difference V Volt, V
Electromotive force E Volt, V
Resistance R Ohm, Ω
Conductance G Siemens, S
Power P Watt, W
Energy W or Eenergy Joule, J

A circuit diagram is a connection model. It is not necessarily a drawing of the physical positions of components on a table or inside an instrument. Components drawn far apart may share the same node through an ideal wire.

Ideal wires have zero resistance. Every point joined by an uninterrupted ideal conductor belongs to the same node and has the same potential. This does not imply that every point in the entire circuit has the same potential; components separate nodes by developing voltage differences.

For a complete resistive circuit, the source and the connected network determine current. A resistor does not consume charge. It converts electrical energy into heat while charge continues through the conducting path.

First Habit

Before calculating, label the requested current direction and voltage polarity. A negative answer reverses the chosen reference. It does not automatically mean an impossible circuit.

Worked Problem 1.1: Interpret a Simple DC Load

Problem: An ideal 12 V source supplies a 6 Ω resistor. Find load current and power, and identify where energy is transferred.

Step 1: Calculate current.

I = V/R

I = 12/6 = 2 A.

Step 2: Calculate load power.

Pload = VI

Pload = 12 × 2 = 24 W.

The resistor absorbs 24 W and converts electrical energy into heat. In this ideal single-load circuit, the source delivers the same 24 W.

The current remains 2 A throughout the unbranched path. The resistor does not use up current as charge passes through it.

2. Electric Charge and Conservation of Charge

Electric charge is a property of matter. The elementary charge magnitude is approximately:

e = 1.602 × 10⁻¹⁹ C

An electron carries charge −e. A collection of n electrons has signed charge:

Q = −ne

When only charge magnitude is requested:

|Q| = ne

The number of particles is positive. The negative sign belongs to the charge carried by each electron and therefore to the collection’s total signed charge.

Electron charge and conventional current direction

Figure 1.2
An electron carries negative charge. Electron motion in a metallic wire is opposite to the conventional current direction used in circuit analysis.

Charge is conserved. It can be transferred or redistributed, but an ordinary resistor does not destroy it. In steady operation, the charge rate entering a two-terminal resistor equals the charge rate leaving it.

This principle is the physical foundation for Kirchhoff’s Current Law. If charge were continually entering a junction faster than it left, charge would accumulate there and the steady-state model would no longer apply.

Common charge units include coulombs, millicoulombs and microcoulombs:

  • 1 mC = 10⁻³ C.
  • 1 µC = 10⁻⁶ C.
  • 1 nC = 10⁻⁹ C.

Even a small charge measured in coulombs corresponds to a very large number of elementary charges.

Numerical Convention

Use the value of elementary charge supplied in the question. If the problem specifies 1.602 × 10⁻¹⁹ C, retain that value consistently rather than changing the precision midway.

Worked Problem 1.2: Count Electrons from Charge Magnitude

Problem: A collection of electrons has charge magnitude 1 µC. Using e = 1.602 × 10⁻¹⁹ C, estimate the number of electrons and the signed charge.

Step 1: Convert the charge magnitude.

|Q| = 1 × 10⁻⁶ C.

Step 2: Calculate the number of electrons.

n = |Q|/e.

n = (1 × 10⁻⁶)/(1.602 × 10⁻¹⁹).

n ≈ 6.2422 × 10¹² electrons.

The signed charge of the collection is:

Q = −1 × 10⁻⁶ C.

Worked Problem 1.3: Count Electrons for a Second Charge

Problem: A collection of electrons has charge magnitude 3.204 µC. Find the number of electrons and the signed charge.

Step 1: Convert the charge.

|Q| = 3.204 × 10⁻⁶ C.

Step 2: Apply the elementary-charge relationship.

n = (3.204 × 10⁻⁶)/(1.602 × 10⁻¹⁹).

n = 2 × 10¹³ electrons.

The collection has signed charge:

Q = −3.204 × 10⁻⁶ C.

DC Source and Load Test

Illustration of a DC source and load test arrangement

Illustration
DC source and load test.

A source transfers energy to a load while charge continues through the circuit. Terminal voltage can differ from EMF under a practical source model. The selected current direction determines the interpretation of a signed current result.

A physical arrangement should always be translated into a clear circuit model before calculation. Leads, component terminals and reference points must correspond to the connections used in the equations.

3. Electric Current: Charge Flow and Reference Direction

Electric current is the rate at which charge passes a cross-section of a conducting path.

Average current is:

Iavg = ΔQ/Δt

For constant current:

Q = It

Instantaneous current is:

i = dQ/dt

The introductory numerical examples use constant current or explicitly stated piecewise-constant intervals.

Charge passing through a conductor cross-section

Figure 1.3
Current through a cross-section measures charge crossing per unit time. It is not the total charge present in the complete conductor.

One ampere means one coulomb per second. A current of 2 A therefore represents a charge-transfer rate of 2 C each second at the selected cross-section.

Conventional current follows the direction positive charge would move. In an ordinary metallic conductor, electrons drift in the opposite direction. Circuit calculations use conventional current.

A current arrow is a reference. If an arrow is drawn from A to B and the solved current is −2 A, the actual conventional current is 2 A from B to A.

Changing an arrow after solving requires changing the sign of its variable. Silently reversing the arrow while retaining the same signed variable creates an inconsistent solution.

Time Conversion

Use seconds with amperes to obtain coulombs. A current of 100 mA for one minute transfers:

Q = 0.1 × 60 = 6 C.

It does not transfer 0.1 C or 100 C. The time conversion must be performed before interpreting the result.

Worked Problem 1.4: Charge Transferred at Constant Current

Problem: A constant 250 mA flows for 120 s. Find charge in coulombs and ampere-hours.

Step 1: Convert current.

I = 250 mA = 0.25 A.

Step 2: Calculate charge in coulombs.

Q = It = 0.25 × 120.

Q = 30 C.

Step 3: Calculate ampere-hours.

Charge = 0.25 × 120/3600.

Charge = 0.00833333 Ah.

Worked Problem 1.5: Charge at a Smaller Current

Problem: A constant 20 mA flows for 300 s. Find transferred charge in coulombs and ampere-hours.

I = 20 mA = 0.02 A.

Q = 0.02 × 300.

Q = 6 C.

Charge in Ah = 0.02 × 300/3600.

Charge = 0.00166667 Ah.

Worked Problem 1.6: Charge at a Larger Current

Problem: A constant 2000 mA flows for 30 s. Find transferred charge.

I = 2000 mA = 2 A.

Q = 2 × 30.

Q = 60 C.

Charge in Ah = 2 × 30/3600.

Charge ≈ 0.0167 Ah.

Worked Problem 1.7: Average Current over Two Intervals

Problem: Current is 2 A for 3 s and 0.5 A for the next 7 s in the same direction. Find total charge and average current.

Step 1: Calculate charge for each interval.

Q1 = 2 × 3 = 6 C.

Q2 = 0.5 × 7 = 3.5 C.

Step 2: Add charge and time.

Qtotal = 6 + 3.5 = 9.5 C.

ttotal = 3 + 7 = 10 s.

Step 3: Calculate average current.

Iavg = 9.5/10.

Iavg = 0.95 A.

The arithmetic average of the two current values would be incorrect because the intervals are unequal. Average current is total transferred charge divided by total elapsed time.

4. Voltage, Potential Difference and Energy per Charge

Voltage between two points expresses electrical potential difference.

Define:

VAB = VA − VB

A voltage of one volt corresponds to one joule of energy transfer per coulomb.

For a constant potential difference, the magnitude of energy transferred is:

W = VQ

The sign of an energy change requires attention to charge sign, motion direction and the chosen energy convention. When a question asks only for magnitude, use the magnitude of the voltage difference and the stated charge magnitude.

Voltage references between two nodes

Figure 1.4
The same two node potentials produce VAB = VA − VB and VBA = −VAB. A voltage statement requires two points or one point and an explicit reference.

The reference node is assigned zero volts by choice. It does not have to be an earth electrode. If VA = 7 V and VB = 2 V relative to a common reference, then VAB = 5 V.

Choosing another reference shifts both node potentials by the same amount but does not change their difference. Circuit behaviour depends on potential differences rather than the arbitrary numerical value assigned to the reference node.

A component’s voltage polarity is independent of its chosen current reference until a sign convention is stated. In a positive resistor, actual conventional current enters the higher-potential terminal.

For a source, current may enter or leave the positive terminal. This distinction determines whether the source absorbs or delivers power.

Common Mistake

Voltage is measured across two points. Current is measured through a branch. Saying that voltage flows through a resistor mixes two different electrical quantities.

Worked Problem 1.8: Node Difference and Reversed Polarity

Problem: VA = 12 V and VB = 5 V relative to a common reference. Find VAB, VBA and the magnitude of energy associated with 2 C crossing this potential difference.

VAB = VA − VB.

VAB = 12 − 5.

VAB = 7 V.

VBA = −VAB.

VBA = −7 V.

Energy magnitude = |VAB|Q = 7 × 2.

Energy magnitude = 14 J.

Worked Problem 1.9: A Negative Node Potential

Problem: VA = 3 V and VB = −2 V. Find VAB, VBA and energy magnitude for 0.5 C.

VAB = 3 − (−2).

VAB = 5 V.

VBA = −5 V.

Energy magnitude = 5 × 0.5.

Energy magnitude = 2.5 J.

Subtracting a negative node potential increases the difference. The reference node does not prevent another node from having a negative potential.

Worked Problem 1.10: Negative Voltage Difference

Problem: VA = −4 V and VB = 1 V. Find VAB, VBA and energy magnitude for 3 C.

VAB = −4 − 1.

VAB = −5 V.

VBA = 5 V.

Energy magnitude = 5 × 3.

Energy magnitude = 15 J.

The negative VAB means A is 5 V below B. It does not mean the voltage difference lacks physical meaning.

5. EMF and Practical Source Terminal Voltage

Electromotive force, or EMF, is energy supplied by a source per unit charge.

E = Energy supplied / Charge

Its unit is the volt. Despite the historical word force, EMF is not a mechanical force measured in newtons.

An ideal voltage source maintains its specified terminal voltage regardless of current in the mathematical model. A practical source may be represented by an ideal EMF E in series with internal resistance r.

Practical source model with internal resistance

Figure 1.5
A practical source is modelled as ideal EMF E in series with internal resistance r. During delivery, internal drop Ir reduces terminal voltage below E.

For the stated series-resistance model delivering current I:

Vterminal = E − Ir

With external load RL:

I = E/(r + RL)

Vterminal = IRL

Internal resistor heating is:

Pinternal = I²r

At open circuit, I = 0 and the model gives Vterminal = E. During delivery through nonzero internal resistance, terminal voltage is below EMF.

If current enters the source’s positive terminal, the source can absorb power. The terminal relationship must then be interpreted using the signed current reference. An unsigned charging current should not be inserted blindly into a discharge formula.

Idealisation

An ideal source’s ability to maintain voltage is a mathematical property of the model. It does not establish that a real battery can provide unlimited current.

Worked Problem 1.11: EMF versus Terminal Voltage

Problem: A source has EMF 12 V and internal resistance 1 Ω. It supplies a 5 Ω load. Find current, terminal voltage and internal power.

I = E/(r + RL).

I = 12/(1 + 5).

I = 2 A.

Vterminal = E − Ir.

Vterminal = 12 − 2 × 1.

Vterminal = 10 V.

Pinternal = I²r = 2² × 1.

Pinternal = 4 W.

Load power is 2² × 5 = 20 W. The ideal EMF supplies 12 × 2 = 24 W, equal to load power plus internal heating.

Worked Problem 1.12: A 9 V Source Model

Problem: E = 9 V, r = 0.5 Ω and RL = 4 Ω. Find current, terminal voltage and internal loss.

I = 9/(0.5 + 4).

I = 2 A.

Vterminal = 9 − 2 × 0.5.

Vterminal = 8 V.

Pinternal = 2² × 0.5.

Pinternal = 2 W.

Worked Problem 1.13: A 6 V Source Model

Problem: E = 6 V, r = 0.2 Ω and RL = 2.8 Ω. Find current, terminal voltage and internal power.

I = 6/(0.2 + 2.8).

I = 2 A.

Vterminal = 6 − 2 × 0.2.

Vterminal = 5.6 V.

Pinternal = 2² × 0.2.

Pinternal = 0.8 W.

The external load receives 5.6 V rather than the complete 6 V EMF because the internal resistance develops a 0.4 V drop.

6. Resistance, Resistivity and Conductor Geometry

Resistance relates the voltage across an element to its current under stated operating conditions.

For a uniform conductor:

R = ρL/A

where:

  • R is resistance in ohms.
  • ρ is resistivity in Ω·m.
  • L is conductor length in metres.
  • A is conducting cross-sectional area in square metres.

Effect of conductor length and area on resistance

Figure 1.6
For the same material and cross-section, a longer conductor has greater resistance. Increasing area provides more conducting cross-section and lowers resistance.

Resistivity is a material property under specified conditions such as temperature. Resistance depends on both the material property and geometry. Their units and meanings are different.

Doubling the length doubles resistance when area and resistivity remain unchanged. Doubling area halves resistance when the other quantities remain unchanged.

If length and area both change, include both factors. For example, doubling length and halving area multiplies resistance by four.

The conducting area is the metal cross-section, not the overall diameter including insulation. When a cable contains a separate return conductor, the specified current path may require including both outgoing and return lengths.

For a positive linear resistor, resistance remains constant within the assumed operating range. Real components have tolerances, temperature dependence and maximum power ratings.

Unit Trap

One square millimetre is:

1 mm² = 10⁻⁶ m²

It is not 10⁻³ m². Area conversion requires squaring the length conversion.

Worked Problem 1.14: Resistance from Geometry

Problem: A conductor has resistivity 1.7 × 10⁻⁸ Ω·m, length 20 m and cross-section 1 mm². Find resistance.

Step 1: Convert area.

A = 1 × 10⁻⁶ m².

Step 2: Apply the conductor formula.

R = ρL/A.

R = (1.7 × 10⁻⁸ × 20)/(1 × 10⁻⁶).

R = 0.34 Ω.

Worked Problem 1.15: A Longer, Thicker Conductor

Problem: Resistivity is 1.7 × 10⁻⁸ Ω·m, length is 50 m and area is 2.5 mm². Find resistance.

A = 2.5 × 10⁻⁶ m².

R = (1.7 × 10⁻⁸ × 50)/(2.5 × 10⁻⁶).

R = 0.34 Ω.

This conductor has the same resistance as the previous example because the increase in length is matched by the increase in conducting area.

Conductor Cross-Section

Illustration of a conductor cross-section

Illustration
Conductor cross-section.

Conductor resistance depends on material, length and cross-sectional area in the stated model. Insulation thickness is not conducting area. Geometry and temperature must be matched when comparing two conductors.

7. Ohm’s Law and the Voltage–Current Characteristic

For an ohmic resistor under constant physical conditions:

V = IR

Equivalent forms are:

I = V/R

R = V/I

The measured voltage and current must refer to the same resistor and use a consistent polarity convention.

Linear voltage-current characteristic of an ohmic resistor

Figure 1.7
A positive linear resistor has a straight voltage-versus-current line through the origin. Its slope is R when voltage is vertical and current horizontal.

When voltage is on the vertical axis and current on the horizontal axis:

Slope = ΔV/ΔI = R

When current is vertical and voltage horizontal:

Slope = ΔI/ΔV = 1/R = G

The axes must therefore be identified before interpreting the slope.

For a nonlinear device, the ratio V/I at one operating point and the local slope need not be equal. Constant-resistance Ohm’s law is a particular linear model.

A resistor does not independently choose both its voltage and its current. The source and network determine their compatible values.

For example, a 10 Ω resistor across 5 V carries 0.5 A. Replacing it with 20 Ω at the same voltage reduces current to 0.25 A.

Model Boundary

Use the constant resistance stated in the problem. Do not introduce diode voltage drops, transistor operating regions or AC reactance into a resistive DC example unless the problem includes those elements.

Worked Problem 1.16: Resistor Current and Power

Problem: A 24 Ω resistor has 12 V across it. Find current and absorbed power.

I = 12/24.

I = 0.5 A = 500 mA.

P = V²/R = 12²/24.

P = 6 W.

Worked Problem 1.17: A Kilohm Resistor

Problem: A 1000 Ω resistor has 5 V across it.

I = 5/1000.

I = 0.005 A = 5 mA.

P = 5²/1000.

P = 0.025 W = 25 mW.

Worked Problem 1.18: A 120 Ω Resistor

Problem: A 120 Ω resistor has 24 V across it.

I = 24/120.

I = 0.2 A = 200 mA.

P = 24²/120.

P = 4.8 W.

Worked Problem 1.19: A 2.2 kΩ Resistor

Problem: A 2200 Ω resistor has 3.3 V across it.

I = 3.3/2200.

I = 0.0015 A = 1.5 mA.

P = 3.3²/2200.

P = 0.00495 W = 4.95 mW.

Worked Problem 1.20: Read a Graph Slope

Problem: A graph has voltage vertical and current horizontal. It passes through 2 V at 0.1 A and 6 V at 0.3 A. Find resistance and the reciprocal graph slope.

R = ΔV/ΔI.

R = (6 − 2)/(0.3 − 0.1).

R = 20 Ω.

For the current-versus-voltage graph:

G = 1/R = 1/20.

G = 0.05 S.

The numerical slope has a different unit when the axes are reversed. The resistance has not changed; only the plotted relationship has been reversed.

8. Conductance and Engineering Units

Conductance is the reciprocal of resistance:

G = 1/R

Its SI unit is the siemens, S.

Ohm’s law can be written:

I = GV

Conductance is useful for parallel networks because parallel branch conductances add directly.

Prefix Multiplier Example
Mega, M 10⁶ 1 MΩ = 1,000,000 Ω
Kilo, k 10³ 1 kΩ = 1000 Ω
Milli, m 10⁻³ 1 mA = 0.001 A
Micro, µ 10⁻⁶ 1 µA = 0.000001 A

A convenient circuit combination is volts divided by kilohms giving milliamperes:

V/kΩ = mA

Similarly:

mA × kΩ = V

Power requires its own unit check:

V × mA = mW

Using A² with Ω gives watts, while using mA² with kΩ gives milliwatts after consistent scaling.

Engineering prefixes and circuit calculation units

Figure 1.8
Keep magnitude and prefix together. A correct circuit equation can still produce a thousand-fold error if kilohms and ohms are mixed.

Reciprocal Check

A resistance of 1 kΩ has conductance 1 mS.

It does not have conductance 1 kS. Taking a reciprocal changes the numerical scale as well as the unit.

Worked Problem 1.21: Resistance to Conductance

Problem: Find conductance of 500 Ω in S and mS, and current at 10 V.

G = 1/500.

G = 0.002 S = 2 mS.

I = GV = 0.002 × 10.

I = 0.02 A = 20 mA.

Worked Problem 1.22: A 2000 Ω Resistance

G = 1/2000.

G = 0.0005 S = 0.5 mS.

At 10 V:

I = 0.0005 × 10.

I = 0.005 A = 5 mA.

Worked Problem 1.23: A 1 MΩ Resistance

G = 1/1,000,000.

G = 1 × 10⁻⁶ S = 0.001 mS.

At 10 V:

I = 10 × 10⁻⁶ A.

I = 10 µA = 0.01 mA.

A large resistance corresponds to a small conductance. This reciprocal behaviour is a useful immediate check before completing a calculation.

9. Nodes, Branches, Loops, Opens and Shorts

A node consists of points joined by ideal conductor. These points share one potential.

A branch is a path between nodes containing an element or a defined series path. A loop is a closed path through the circuit. A mesh is a loop containing no other loop inside it in a planar circuit drawing.

Nodes, junctions and branch connections

Figure 1.9
Junction dots identify connected branches. Series and parallel relationships depend on shared nodes rather than whether symbols appear side by side.

Two resistors are in series when the same current must pass through both without dividing at their common junction.

Two resistors are in parallel when both terminals share the same two nodes. Sharing only one node does not make them parallel.

A bridge-shaped network may not permit an immediate series or parallel reduction. The arrangement of symbols can hide the actual node relationships, so node labels should be established before combining components.

An ideal open branch enforces:

Iopen = 0

It can support a nonzero terminal voltage.

An ideal short circuit enforces:

Vshort = 0

It can carry a nonzero current determined by the surrounding network.

A resistor bypassed by an ideal wire has zero voltage across it. Therefore its current is zero for a positive finite resistance, while the wire may carry the complete path current.

Redraw Intelligently

Move ideal wires and stretch the drawing without changing connectivity. Label the nodes before deciding which components combine.

A redraw is useful only when it preserves every connection. Accidentally joining two distinct nodes produces a different circuit.

Worked Problem 1.24: Open Load with a Series Resistor

Problem: A 12 V source connects through 1 kΩ to open terminal a. Terminal b is the source negative reference. Find current, resistor drop and Vab.

The open output prevents a complete current path.

I = 0 A.

Resistor drop:

VR = IR = 0 × 1000.

VR = 0 V.

Terminal a remains at source positive potential:

Vab = 12 V.

An open branch can therefore have a nonzero voltage even though its current is zero.

Worked Problem 1.25: A Bypassed Resistor

Problem: A 10 Ω resistor is connected in parallel with an ideal wire between A and B. The surrounding circuit carries 2 A through the combined path. Find resistor voltage and current.

The wire forces:

VAB = 0 V.

The resistor shares those terminals:

Iresistor = 0/10.

Iresistor = 0 A.

The stated 2 A therefore passes through the ideal wire in this model.

10. Resistors Connected in Series

Series resistors carry the same branch current.

Applying KVL:

V = IR1 + IR2 + IR3 + …

Factoring out current:

V = I(R1 + R2 + R3 + …).

Therefore:

Req = R1 + R2 + R3 + …

Series resistor network with common current

Figure 1.10
A single current passes through all series elements. Individual drops add, and each drop follows the current through its positive resistance.

For a source V across the complete chain:

I = V/Req

Individual drops are:

Vi = IRi

The total positive series resistance is greater than any individual constituent.

For n identical resistors:

Req = nR

If one element becomes open, the ideal series-path current becomes zero. The resulting voltage distribution must be reconsidered; the previous operating drops cannot simply be retained.

Series resistors do not necessarily dissipate equal power. Since current is common:

Pi = I²Ri

The larger resistance dissipates more power at that common current.

Sanity Check

If a positive series equivalent is smaller than one of its components, either the topology or the arithmetic is wrong.

Worked Problem 1.26: Series Equivalent, Drops and Powers

Problem: A 12 V source drives 2 Ω, 4 Ω and 6 Ω in series.

Req = 2 + 4 + 6.

Req = 12 Ω.

I = 12/12.

I = 1 A.

Individual drops:

  • V1 = 1 × 2 = 2 V.
  • V2 = 1 × 4 = 4 V.
  • V3 = 1 × 6 = 6 V.

Individual powers:

  • P1 = 1² × 2 = 2 W.
  • P2 = 1² × 4 = 4 W.
  • P3 = 1² × 6 = 6 W.

The drops add to 12 V and the powers add to source power, 12 W.

Worked Problem 1.27: A 24 V Series Network

Problem: A 24 V source drives 3 Ω, 5 Ω and 4 Ω in series.

Req = 3 + 5 + 4.

Req = 12 Ω.

I = 24/12.

I = 2 A.

Drops in listed order are:

6 V, 10 V and 8 V.

Powers in listed order are:

12 W, 20 W and 16 W.

Total absorbed power is 48 W, equal to 24 × 2.

Resistors Connected in a Single Path

Illustration of resistors connected in a single path

Illustration
Resistors connected in a single path.

Series elements share branch current. Their individual drops and powers depend on their resistance values. Schematic connections rather than physical spacing define the series relationship.

Worked Problem 1.28: Series Resistors in Ohms

Problem: A 9 V source drives 150 Ω, 300 Ω and 450 Ω in series.

Req = 150 + 300 + 450.

Req = 900 Ω.

I = 9/900.

I = 0.01 A = 10 mA.

Drops are:

1.5 V, 3 V and 4.5 V.

Powers are:

0.015 W, 0.03 W and 0.045 W.

Their sum is 0.09 W, equal to source power 9 × 0.01.

11. Resistors Connected in Parallel

Parallel resistors share the same two terminal nodes. Therefore they have the same voltage.

For parallel branches:

I1 = V/R1.

I2 = V/R2.

I3 = V/R3.

KCL gives:

It = V/R1 + V/R2 + V/R3.

Therefore:

1/Req = 1/R1 + 1/R2 + 1/R3 + …

For two resistors:

Req = R1R2/(R1 + R2)

Parallel resistors with common voltage and divided current

Figure 1.11
Both branches have the same voltage. Their currents add at the source and divide inversely with resistance.

For positive finite parallel resistors, equivalent resistance is smaller than the smallest branch resistance.

For n equal branches:

Req = R/n

A lower-resistance branch draws more current at the common voltage. Adding another positive parallel branch increases total conductance and reduces equivalent resistance.

Under an ideal fixed-voltage source, existing branch voltages remain unchanged when another parallel branch is added. A practical source with internal resistance can behave differently because its terminal voltage depends on total current.

Two-Resistor Shortcut

The product-over-sum formula applies directly to two parallel resistors. For three or more resistors, use the reciprocal sum or combine a valid pair first.

Do not multiply all resistances and divide by their simple sum for a three-branch network. That expression is not the general parallel formula.

Worked Problem 1.29: Two Parallel Branches

Problem: Resistors 6 Ω and 12 Ω are connected across 12 V.

1/Req = 1/6 + 1/12.

Req = 4 Ω.

I1 = 12/6.

I1 = 2 A.

I2 = 12/12.

I2 = 1 A.

It = 2 + 1.

It = 3 A.

Source current from the equivalent is 12/4 = 3 A, confirming the result.

Worked Problem 1.30: Three Parallel Branches

Problem: Resistors 12 Ω, 24 Ω and 8 Ω are connected across 24 V.

1/Req = 1/12 + 1/24 + 1/8.

Req = 4 Ω.

Branch currents are:

  • I1 = 24/12 = 2 A.
  • I2 = 24/24 = 1 A.
  • I3 = 24/8 = 3 A.

It = 6 A.

The 8 Ω branch draws the greatest current because it has the smallest resistance.

Worked Problem 1.31: Parallel Kilohm Resistors

Problem: Resistors 1000 Ω and 2000 Ω are across 5 V.

Req = (1000 × 2000)/(1000 + 2000).

Req = 666.6667 Ω.

I1 = 5/1000 = 5 mA.

I2 = 5/2000 = 2.5 mA.

It = 7.5 mA.

Parallel Load Branches

Illustration of parallel load branches

Illustration
Parallel load branches.

Parallel branches share one node-pair voltage while current divides. Branch currents add at the junction. A negative signed result reverses the chosen reference direction without invalidating charge conservation.

12. Series–Parallel Network Reduction

A mixed resistor network is reduced one valid combination at a time.

The basic procedure is:

  • Identify the actual nodes.
  • Find a genuine series chain or parallel group.
  • Replace that group with its equivalent.
  • Redraw the remaining circuit.
  • Continue until the source sees one equivalent resistance.
  • Calculate source current.
  • Work backward to recover original branch voltages and currents.

Series resistor feeding a parallel pair

Figure 1.12
R1 is in series with the parallel pair R2 and R3. Source current passes through R1 before dividing between the lower branches.

For R1 in series with R2 parallel to R3:

Rp = R2R3/(R2 + R3)

Rt = R1 + Rp

It = Vs/Rt

Vparallel = ItRp

I2 = Vparallel/R2

I3 = Vparallel/R3

Do not use the complete source voltage across R2 or R3 when R1 develops a nonzero series drop.

Do not assign source current to every parallel branch. Source current divides at the junction, and the individual branch currents must add back to it.

Verification Habit

Check KCL at the current split and KVL around either complete source-to-return path. In a purely resistive ideal-source network, total resistor power must equal source power.

Worked Problem 1.32: Reduce and Recover Every Branch

Worked series-parallel circuit for problem 1.32

Figure 1.13
R1 lies before the current split. R2 and R3 share the same two nodes.

Problem: A 12 V source drives 2 Ω in series with 6 Ω parallel to 3 Ω.

Rp = (6 × 3)/(6 + 3).

Rp = 2 Ω.

Rt = 2 + 2.

Rt = 4 Ω.

It = 12/4.

It = 3 A.

Vparallel = 3 × 2.

Vparallel = 6 V.

I2 = 6/6.

I2 = 1 A.

I3 = 6/3.

I3 = 2 A.

The branch currents add to 3 A. The series resistor drops 6 V, leaving 6 V across the parallel combination.

Worked Problem 1.33: A Scaled Mixed Network

Worked series-parallel circuit for problem 1.33

Figure 1.14
The series resistance carries total current before it splits into the parallel branches.

Problem: Vs = 24 V, R1 = 4 Ω, R2 = 12 Ω and R3 = 6 Ω.

Rp = (12 × 6)/(12 + 6).

Rp = 4 Ω.

Rt = 4 + 4.

Rt = 8 Ω.

It = 24/8.

It = 3 A.

Vparallel = 3 × 4.

Vparallel = 12 V.

I2 = 12/12 = 1 A.

I3 = 12/6 = 2 A.

The current split is 1 A and 2 A.

Worked Problem 1.34: Equal Parallel Branches

Worked mixed circuit with equal parallel resistors

Figure 1.15
Equal lower branches share both terminals and therefore receive equal currents.

Problem: Vs = 10 V, R1 = 1000 Ω, R2 = 2000 Ω and R3 = 2000 Ω.

Rp = 2000/2.

Rp = 1000 Ω.

Rt = 1000 + 1000.

Rt = 2000 Ω.

It = 10/2000.

It = 5 mA.

Vparallel = 0.005 × 1000.

Vparallel = 5 V.

I2 = 5/2000 = 2.5 mA.

I3 = 5/2000 = 2.5 mA.

The equal branch currents add to 5 mA as required.

Worked Problem 1.35: Unequal Lower Branches

Worked mixed circuit with unequal parallel branches

Figure 1.16
Branch currents depend on the common parallel voltage and individual branch resistances.

Problem: Vs = 18 V, R1 = 3 Ω, R2 = 12 Ω and R3 = 4 Ω.

Rp = (12 × 4)/(12 + 4).

Rp = 3 Ω.

Rt = 3 + 3.

Rt = 6 Ω.

It = 18/6.

It = 3 A.

Vparallel = 3 × 3.

Vparallel = 9 V.

I2 = 9/12.

I2 = 0.75 A.

I3 = 9/4.

I3 = 2.25 A.

The lower-resistance branch receives three times the current of the higher-resistance branch.

13. Voltage-Divider Rule

An unloaded voltage divider consists of series resistors across a source, with output measured across a selected resistor or series group.

For R1 and R2 across Vs:

I = Vs/(R1 + R2).

Voltage across R2 is:

Vout = IR2.

Therefore:

Vout = VsR2/(R1 + R2)

For a larger series chain:

Vi = VsRi/ΣR

Unloaded voltage divider and output terminals

Figure 1.17
Output is measured from the tap to reference across the lower resistor. The basic equation assumes no additional load current leaves the tap.

The output fraction depends on the resistance ratio. Total divider current depends on total resistance.

Scaling both resistors by the same positive factor preserves unloaded output voltage. However, it changes divider current, resistor power and sensitivity to an external load.

For a desired fraction a = Vout/Vs:

R2/R1 = a/(1 − a)

This applies for 0 < a < 1 in the simple positive-resistance ground-referenced divider.

Do Not Memorise Blindly

Mark output terminals before selecting the numerator. Voltage across R1 uses R1 in the numerator, while voltage across R2 uses R2.

A passive unloaded divider cannot produce an output larger than the applied source magnitude under this simple arrangement.

Worked Problem 1.36: Unloaded Divider

Problem: Vs = 12 V, R1 = 2000 Ω and R2 = 1000 Ω. Find output across R2 and divider current.

I = 12/(2000 + 1000).

I = 4 mA.

Vout = 12 × 1000/3000.

Vout = 4 V.

The upper resistor develops the remaining 8 V.

Worked Problem 1.37: A 10 V Divider

Problem: Vs = 10 V, R1 = 3000 Ω and R2 = 2000 Ω.

I = 10/5000.

I = 2 mA.

Vout = 10 × 2000/5000.

Vout = 4 V.

Worked Problem 1.38: Equal Divider Resistors

Problem: Vs = 5 V and both resistors are 10 kΩ.

I = 5/20,000.

I = 0.25 mA.

Vout = 5 × 10,000/20,000.

Vout = 2.5 V.

Equal series resistances divide the applied voltage equally when the output is unloaded.

Worked Problem 1.39: A One-Quarter Output

Problem: Vs = 24 V, R1 = 15 kΩ and R2 = 5 kΩ.

I = 24/20,000.

I = 1.2 mA.

Vout = 24 × 5000/20,000.

Vout = 6 V.

The lower resistor is one quarter of total resistance, so its voltage is one quarter of the source.

14. Loaded Voltage Divider and Measurement Loading

A load RL connected from the divider tap to reference is in parallel with the lower resistor R2.

The lower equivalent becomes:

Rlower = R2 || RL

The loaded output is:

Vout = Vs(R2 || RL)/[R1 + (R2 || RL)]

Loaded voltage divider with a parallel external load

Figure 1.18
RL shares both terminals with R2. Current through R1 splits between R2 and RL, so R1 and R2 no longer carry the same current.

The original unloaded divider ratio is no longer exact after connecting a finite load.

A voltmeter with finite input resistance acts as a load. A high input resistance reduces loading error, but the error is not mathematically zero unless an ideal meter model is used.

For positive resistors under an ideal fixed source, a finite load across the lower leg reduces that leg’s equivalent resistance and lowers the tap voltage.

Choosing smaller divider resistors can reduce relative loading for a given external load, but increases divider current and power consumption.

Practical Interpretation

A divider is a voltage-scaling network. It does not automatically behave as a regulated power supply for a changing load.

The current through the upper resistor is the sum of lower-resistor current and external load current. Therefore load current must not be confused with total divider input current.

Worked Problem 1.40: Divider Loading Error

Loaded divider for problem 1.40

Figure 1.19
RL is connected across R2, creating a current split at the output node.

Problem: Vs = 12 V, R1 = 2000 Ω, R2 = 1000 Ω and RL = 1000 Ω.

Rlower = 1000 || 1000.

Rlower = 500 Ω.

Vloaded = 12 × 500/(2000 + 500).

Vloaded = 2.4 V.

IL = 2.4/1000.

IL = 2.4 mA.

Unloaded voltage:

V0 = 12 × 1000/3000.

V0 = 4 V.

Percentage reduction:

Reduction = (4 − 2.4)/4 × 100.

Reduction = 40%.

Worked Problem 1.41: Equal Divider and Load Resistances

Loaded divider for problem 1.41

Figure 1.20
Equal lower and load resistances halve the effective lower-leg resistance.

Problem: Vs = 10 V, R1 = 10 kΩ, R2 = 10 kΩ and RL = 10 kΩ.

Rlower = 10 kΩ || 10 kΩ.

Rlower = 5 kΩ.

Vloaded = 10 × 5/(10 + 5).

Vloaded ≈ 3.3333 V.

IL = 3.3333/10,000.

IL ≈ 0.3333 mA.

Unloaded voltage is 5 V.

Reduction = (5 − 3.3333)/5 × 100.

Reduction ≈ 33.3333%.

Worked Problem 1.42: A Relatively Light Load

Loaded divider for problem 1.42

Figure 1.21
A larger load resistance creates a smaller loading effect, while the output remains below its unloaded value.

Problem: Vs = 5 V, R1 = 1000 Ω, R2 = 1000 Ω and RL = 10,000 Ω.

Rlower = (1000 × 10,000)/(1000 + 10,000).

Rlower ≈ 909.0909 Ω.

Vloaded = 5 × 909.0909/(1000 + 909.0909).

Vloaded ≈ 2.381 V.

IL = 2.381/10,000.

IL ≈ 0.2381 mA.

Unloaded voltage is 2.5 V.

Percentage reduction ≈ 4.7619%.

Worked Problem 1.43: A 24 V Loaded Divider

Loaded divider for problem 1.43

Figure 1.22
The same loaded-divider method applies after combining the lower resistor and external load.

Problem: Vs = 24 V, R1 = 6000 Ω, R2 = 3000 Ω and RL = 6000 Ω.

Rlower = 3000 || 6000.

Rlower = 2000 Ω.

Vloaded = 24 × 2000/(6000 + 2000).

Vloaded = 6 V.

IL = 6/6000.

IL = 1 mA.

Unloaded output is:

V0 = 24 × 3000/9000 = 8 V.

Percentage reduction = 25%.

15. Current-Divider Rule

Parallel branches have the same voltage. Their currents are inversely proportional to their resistances.

For two branches:

I1 = ItR2/(R1 + R2)

I2 = ItR1/(R1 + R2)

The opposite resistor appears in each numerator.

Current division between two parallel branches

Figure 1.23
Supplied current divides between resistive branches. The lower-resistance branch receives the larger current.

For several parallel branches, conductance gives:

Ii = ItGi/ΣG

This follows because each branch current is GiV and total current is VΣG.

Confirm that the branches share both nodes before applying the rule. Components are not a current divider merely because they appear below the same line in a drawing.

If an ideal voltage source fixes the branch voltage, the currents can instead be found directly from V/R. Both approaches agree when applied to the same circuit.

Fast Checks

  • Branch currents must add to total current.
  • Equal parallel resistances receive equal currents.
  • The smaller positive resistance receives the larger current.
  • The common voltage calculated from either branch must agree.

Worked Problem 1.44: A 3 A Current Divider

Problem: Total current is 3 A through parallel 6 Ω and 3 Ω branches.

I1 through 6 Ω:

I1 = 3 × 3/(6 + 3).

I1 = 1 A.

I2 through 3 Ω:

I2 = 3 × 6/(6 + 3).

I2 = 2 A.

Common voltage:

V = 1 × 6 = 2 × 3.

V = 6 V.

Worked Problem 1.45: A 6 A Current Divider

Problem: It = 6 A, R1 = 4 Ω and R2 = 8 Ω.

I1 = 6 × 8/(4 + 8).

I1 = 4 A.

I2 = 6 × 4/(4 + 8).

I2 = 2 A.

V = 4 × 4 = 2 × 8.

V = 16 V.

Worked Problem 1.46: Current Division in Milliamperes

Problem: It = 12 mA, R1 = 1 kΩ and R2 = 2 kΩ.

I1 = 12 × 2/(1 + 2).

I1 = 8 mA.

I2 = 12 × 1/(1 + 2).

I2 = 4 mA.

Common voltage:

V = 8 mA × 1 kΩ.

V = 8 V.

Worked Problem 1.47: A 10 mA Divider

Problem: It = 10 mA, R1 = 3 kΩ and R2 = 6 kΩ.

I1 = 10 × 6/(3 + 6).

I1 ≈ 6.6667 mA.

I2 = 10 × 3/(3 + 6).

I2 ≈ 3.3333 mA.

V = 6.6667 mA × 3 kΩ.

V = 20 V.

The results satisfy the inverse-resistance relationship and add to the supplied current.

16. Power in DC Resistive Circuits

Electrical power is the rate at which energy is transferred.

Under the passive sign convention:

p = vi

when current enters the labelled positive-voltage terminal.

For a positive resistor:

P = VI = I²R = V²/R

Absorbed resistor power is nonnegative.

Passive sign convention for resistor power

Figure 1.24
A resistor absorbs power when current enters its positive terminal. Voltage and current must use matching references.

Use I²R when resistor current is known. Use V²/R when the resistor voltage is known.

A fixed-voltage comparison and a fixed-current comparison produce different trends:

  • At fixed voltage, increasing R reduces power because P = V²/R.
  • At fixed current, increasing R increases power because P = I²R.

These statements are consistent because the controlled quantity differs.

A resistor may have the required resistance value while being inadequately rated for calculated dissipation. Compare operating power with the supplied allowable rating under its stated conditions.

Unit Check

12 V × 20 mA = 240 mW = 0.24 W.

Writing 240 W would introduce a thousand-fold error.

Worked Problem 1.48: Rating Assessment

Problem: A 120 Ω resistor has 12 V across it. Its stated allowable dissipation is 0.5 W.

I = 12/120.

I = 0.1 A.

P = 12²/120.

P = 1.2 W.

Since 1.2 W exceeds 0.5 W, the stated nominal condition fails the rating comparison.

Worked Problem 1.49: A Lower Dissipation

Problem: A 100 Ω resistor has 5 V across it and a stated allowable dissipation of 0.5 W.

I = 5/100.

I = 0.05 A.

P = 5²/100.

P = 0.25 W.

The calculated dissipation is below the stated 0.5 W limit under the assumed conditions.

Worked Problem 1.50: A 24 V Load Resistor

Problem: A 240 Ω resistor has 24 V across it. Its allowable dissipation is stated as 3 W.

I = 24/240.

I = 0.1 A.

P = 24²/240.

P = 2.4 W.

The nominal comparison passes because 2.4 W is below 3 W. The assessment uses the specified operating and rating assumptions.

Resistive Load and Power Dissipation

Illustration of a resistive load dissipating power

Illustration
Resistive load and power dissipation.

A resistive load converts electrical energy into heat. Matching current and voltage are required for power calculation. Component size or the presence of a heat sink alone does not establish an acceptable temperature.

17. Source Power, Absorption and Power Balance

A source may supply or absorb energy depending on current direction relative to its voltage polarity.

Under the passive sign convention:

  • Positive p = vi means absorption.
  • Negative p = vi means delivery.

The word source identifies a circuit model. It does not mean that its power must always be negative.

Source delivering and absorbing power

Figure 1.25
Current leaving a source’s positive terminal corresponds to delivery. Current entering that terminal corresponds to absorption.

For a complete ideal resistive DC network:

Σp = 0

Equivalently:

Total delivered power = Total absorbed power

Include every source and resistor within the chosen circuit boundary.

When two voltage sources oppose through a resistor, the larger source can deliver energy partly to the resistor and partly to the other source model.

This is a mathematical statement about the supplied ideal models. It does not define a charging method for an arbitrary real battery.

Final Sign Check

Do not force every source power to be negative. Determine its sign from the solved current and marked voltage polarity.

A source whose current is zero has zero power even if its voltage is nonzero.

Worked Problem 1.51: One Source Delivers and Another Absorbs

Problem: Sources E1 = 12 V and E2 = 6 V have negative terminals joined. A 3 Ω resistor connects their positive terminals. Define current from E1 positive toward E2 positive.

I = (12 − 6)/3.

I = 2 A.

Current leaves E1 positive, so:

pE1 = −12 × 2.

pE1 = −24 W.

Current enters E2 positive, so:

pE2 = 6 × 2.

pE2 = 12 W.

Resistor power:

pR = 2² × 3.

pR = 12 W.

Power balance:

−24 + 12 + 12 = 0.

Worked Problem 1.52: A Second Opposing-Source Circuit

Problem: E1 = 10 V, E2 = 4 V and R = 2 Ω with the same references.

I = (10 − 4)/2.

I = 3 A.

pE1 = −10 × 3.

pE1 = −30 W.

pE2 = 4 × 3.

pE2 = 12 W.

pR = 3² × 2.

pR = 18 W.

Power balance:

−30 + 12 + 18 = 0.

Isolated Low-Voltage Bench Supply

Illustration of an isolated low-voltage bench supply

Illustration
Isolated low-voltage bench supply.

A supply provides circuit energy while the selected model defines its terminal voltage and internal behaviour. Current limiting and load conditions affect a real output.

A displayed setting should not be confused with a guaranteed voltage at every point in a loaded circuit. Lead resistance and internal source behaviour may matter when included in the model.

18. Energy, Watt-Hours and Running Cost

Power is an energy-transfer rate. Energy accumulates over time.

For constant power:

W = Pt

With P in watts and t in seconds, W is in joules.

With P in watts and t in hours, energy is in watt-hours.

1 Wh = 3600 J

1 kWh = 3.6 × 10⁶ J

Energy represented by area under a constant-power graph

Figure 1.26
Power gives the height and operating time gives the width. Their product is energy.

For a supplied tariff calculation:

Cost = Energy in kWh × Rate per kWh

Add other charges only when the question specifies them.

The numerical tariffs below are hypothetical supplied values. They are used to demonstrate the calculation rather than represent a current electricity price.

For several loads or operating states:

Wtotal = ΣPiti

Charge capacity in Ah is not energy by itself. A voltage model is required to convert charge transfer into electrical energy.

Numerical Habit

Convert minutes to hours for Wh or to seconds for J. Carry the units through the multiplication.

Do not multiply a value in watts by minutes and then label the answer Wh without conversion.

Worked Problem 1.53: Energy and Hypothetical Cost

Problem: A 100 W load runs for 5 h. The supplied tariff is 8 currency units/kWh.

Energy = 100 × 5.

Energy = 500 Wh = 0.5 kWh.

In joules:

W = 500 × 3600.

W = 1,800,000 J.

Cost = 0.5 × 8.

Cost = 4 currency units.

Worked Problem 1.54: A 60 W Load

Problem: A 60 W load runs for 8 h. The hypothetical tariff is 7 currency units/kWh.

Energy = 60 × 8.

Energy = 480 Wh = 0.48 kWh.

W = 480 × 3600.

W = 1,728,000 J.

Cost = 0.48 × 7.

Cost = 3.36 currency units.

Worked Problem 1.55: A Higher-Power Load for a Shorter Time

Problem: A 1500 W load runs for 0.5 h. The supplied tariff is 6.5 currency units/kWh.

Energy = 1500 × 0.5.

Energy = 750 Wh = 0.75 kWh.

W = 750 × 3600.

W = 2,700,000 J.

Cost = 0.75 × 6.5.

Cost = 4.875 currency units.

Worked Problem 1.56: Two Operating States

Problem: A device draws 20 W for 2 h and 2 W for another 10 h. Find total energy and average power over those 12 h.

W1 = 20 × 2 = 40 Wh.

W2 = 2 × 10 = 20 Wh.

Wtotal = 60 Wh.

Pavg = Wtotal/ttotal.

Pavg = 60/12.

Pavg = 5 W.

The average is weighted by operating duration. It is not the arithmetic mean of 20 W and 2 W because those states last for different times.

19. Internal Resistance and Load Regulation

For a source with EMF E and series internal resistance r supplying RL:

I = E/(r + RL)

Terminal voltage is:

Vterminal = ERL/(r + RL)

Reducing RL increases current. The larger internal drop Ir then lowers terminal voltage in this model.

Internal source drop and external load voltage

Figure 1.27
The load receives terminal voltage after internal drop. Internal and external powers are separate parts of source-energy balance.

The internal resistance can represent a simplified source resistance or wiring resistance. It is separate from external load resistance.

If open-circuit EMF E and loaded terminal voltage V at current I are known:

r = (E − V)/I

This form uses the delivering-current convention.

At a mathematical external short with nonzero r, current is E/r and external terminal voltage is zero. Real sources may include additional protection and current-limit behaviour beyond this simple linear model.

Useful Comparison

An ideal source and a practical source can predict different effects when an additional parallel load is attached.

An ideal voltage source maintains branch voltage. A practical source may develop a greater internal drop because total current increases.

Worked Problem 1.57: Infer Internal Resistance

Problem: Open-circuit EMF is 12 V. At a delivered current of 2 A, terminal voltage is 11 V.

r = (12 − 11)/2.

r = 0.5 Ω.

Connected load resistance:

RL = 11/2.

RL = 5.5 Ω.

Internal drop is 1 V, consistent with 2 × 0.5.

Worked Problem 1.58: A 9 V Source

Problem: E = 9 V, terminal voltage is 8.4 V and current is 0.6 A.

r = (9 − 8.4)/0.6.

r = 1 Ω.

RL = 8.4/0.6.

RL = 14 Ω.

Worked Problem 1.59: A 6 V Source

Problem: E = 6 V, terminal voltage is 5.4 V and current is 1.5 A.

r = (6 − 5.4)/1.5.

r = 0.4 Ω.

RL = 5.4/1.5.

RL = 3.6 Ω.

The source model can now be used for another load only while its assumed linear behaviour remains applicable.

20. Kirchhoff’s Current Law

Kirchhoff’s Current Law states that the algebraic sum of currents at a node is zero in the steady lumped-circuit model.

ΣI = 0

An equivalent statement is:

Total current entering = Total current leaving

The law follows from conservation of charge when no net charge accumulates at the node.

Current directions at a junction for KCL

Figure 1.28
Arrows identify entering and leaving currents. An unknown current can solve negative if actual current opposes its assigned arrow.

Choose one consistent convention:

  • All currents leaving positive.
  • All currents entering positive.
  • Entering currents on one side and leaving currents on the other.

The conventions are equivalent when signs are handled consistently.

If 5 A and 2 A enter while 3 A and Ix leave:

5 + 2 = 3 + Ix.

Therefore Ix = 4 A.

A node can extend along an ideal wire containing several drawn junction dots. Those dots do not create separate node voltages when joined directly by ideal conductor.

KCL can also be applied to a larger closed boundary if every current crossing the boundary is included.

Avoid This Error

Current is not used up by a resistor. Current may split at a junction, but its algebraic balance remains zero.

A negative solved current should remain signed in the node equation and then be described in words using its actual direction.

Worked Problem 1.60: Positive Unknown Leaving Current

Problem: Currents 5 A and 2 A enter. A known 3 A leaves. Ix is referenced leaving.

7 = 3 + Ix.

Ix = 4 A leaving.

The positive result confirms the assigned leaving direction.

Worked Problem 1.61: KCL in Smaller Currents

Problem: Currents 0.02 A and 0.03 A enter. A known 0.01 A leaves. Ix is referenced leaving.

0.02 + 0.03 = 0.01 + Ix.

Ix = 0.04 A = 40 mA leaving.

All currents must use a consistent unit scale when substituted into the equation.

Worked Problem 1.62: Negative Unknown Current

Problem: Currents 1 A and 2 A enter. A known 5 A leaves. Ix is assumed leaving.

1 + 2 = 5 + Ix.

Ix = −2 A.

Actual current is:

2 A entering the node.

The negative result supplies the direction needed to satisfy charge conservation.

Worked Problem 1.63: A Negative Milliampere Result

Problem: Currents 6 mA and 4 mA enter. A known 12 mA leaves. Ix is referenced leaving.

6 + 4 = 12 + Ix.

Ix = −2 mA.

The physical current is 2 mA entering. Replacing the signed answer by positive 2 mA without reversing the interpreted direction would be incorrect.

21. Kirchhoff’s Voltage Law

Kirchhoff’s Voltage Law states that the algebraic sum of voltage changes around a closed path is zero for the lumped DC model.

ΣV = 0

A complete traversal returns to the initial potential. The law expresses consistent potential differences and energy transfer around the path.

KVL loop with source rise and resistor drops

Figure 1.29
Crossing the source from negative to positive gives a rise E. Traversing a resistor with current gives a drop IR.

For resistor traversal:

  • With its referenced current, use −IR as the potential change.
  • Against its referenced current, use +IR.

For an ideal voltage source:

  • From − to +, use +E.
  • From + to −, use −E.

The source sign follows its polarity and traversal direction. It does not follow whether the source is drawn on the left or the right.

Reversing loop traversal multiplies every term by −1. It does not change the physical solution.

Self-Check

Never reverse only one term when reversing loop direction. Every potential change must follow the same traversal.

The same KVL equation can be written as rises equal drops or as an algebraic sum equal to zero.

Worked Problem 1.64: Solve a Single Loop

Problem: A 12 V source drives series 2 Ω and 4 Ω resistors.

Traverse from source negative to positive and then through the resistors with current.

12 − 2I − 4I = 0.

12 − 6I = 0.

I = 2 A.

Drops:

V1 = 2 × 2 = 4 V.

V2 = 2 × 4 = 8 V.

4 + 8 = 12 V.

Adjustable Resistance

A potentiometer can provide an adjustable divider. Its wiper voltage depends on connection and loading.

The total end-to-end resistance and the separate wiper segments are different quantities. Apply a divider equation only after identifying which segment is upper, which is lower and whether the wiper is loaded.

Worked Problem 1.65: A Kilohm Loop

Problem: A 10 V source drives 1 kΩ and 4 kΩ in series.

KVL:

10 − 1000I − 4000I = 0.

I = 10/5000.

I = 2 mA.

Drops:

V1 = 2 V.

V2 = 8 V.

The sum is 10 V.

Worked Problem 1.66: A 9 V Loop

Problem: A 9 V source drives 300 Ω and 600 Ω.

9 − 300I − 600I = 0.

I = 9/900.

I = 10 mA.

Drops:

V1 = 0.01 × 300 = 3 V.

V2 = 0.01 × 600 = 6 V.

3 + 6 = 9 V.

22. Branch Currents and Reference Choices

A branch current is the physical current through a selected branch with an assigned direction.

It is not always identical to a mesh-current variable. In a branch shared by two meshes, the physical branch current is an algebraic combination of the mesh currents.

For a resistor between A and B with current referenced from A to B:

IAB = (VA − VB)/R

Reversing the reference gives:

IBA = −IAB

Current through a resistor between two non-ground nodes

Figure 1.30
The A-to-B current is determined by VA − VB. If B is at a higher potential, the A-to-B result is negative.

Resistor power remains:

P = IAB²R

It is independent of the arbitrary arrow direction because the current is squared.

A negative node voltage means the node is below the chosen reference. A negative branch current means current opposes the chosen arrow. Neither result should be rejected solely because it is negative.

Distinguish Quantities

A negative resistor voltage paired with a negative passive-reference current still gives positive absorbed power.

Signs describe references. A positive resistor does not become an energy source merely because one reference variable is negative.

Worked Problem 1.67: Positive A-to-B Current

Problem: VA = 8 V, VB = 2 V and R = 3 Ω.

IAB = (8 − 2)/3.

IAB = 2 A.

P = 2² × 3.

P = 12 W.

Current flows from A toward B because A has the higher potential.

Worked Problem 1.68: Negative A-to-B Current

Problem: VA = 1 V, VB = 5 V and R = 2 Ω.

IAB = (1 − 5)/2.

IAB = −2 A.

Actual current is 2 A from B toward A.

P = (−2)² × 2.

P = 8 W.

Worked Problem 1.69: A Negative Node Potential

Problem: VA = −3 V, VB = 1 V and R = 1000 Ω.

IAB = (−3 − 1)/1000.

IAB = −4 mA.

Actual current is 4 mA from B to A.

P = 0.004² × 1000.

P = 0.016 W = 16 mW.

23. Nodal Analysis: Systematic Procedure

Nodal analysis finds node potentials relative to a chosen reference using KCL and component voltage-current relations.

The procedure is:

  • Choose a convenient reference node.
  • Label all other node potentials.
  • Identify any potentials fixed directly by ideal voltage sources.
  • Write KCL at each unknown node.
  • Express resistor currents using actual terminal differences.
  • Solve the resulting linear equations.
  • Recover requested branch currents, voltages and powers.
  • Check signed KCL and power balance.

Nodal analysis procedure and reference node

Figure 1.31
Define node potentials, write branch currents from voltage differences and then apply KCL.

For an unknown node A connected to known potentials V1 and V2 and to ground:

(VA − V1)/R1 + (VA − V2)/R2 + VA/Rg = 0

This is an all-leaving-current equation.

A source connected directly between a node and reference can fix that node potential immediately. More complicated source placements may require supernode analysis, which is beyond the simple introductory networks considered here.

Equation Check

Every resistor term needs the starting-node potential minus the ending-node potential.

Writing VA/R for every branch is correct only when every other endpoint is actually ground.

Worked Problem 1.70: Build One KCL Equation

Problem: A connects through 2 Ω to 12 V, through 3 Ω to 6 V and through 6 Ω to ground.

KCL:

(VA − 12)/2 + (VA − 6)/3 + VA/6 = 0.

Multiply by 6:

3VA − 36 + 2VA − 12 + VA = 0.

6VA − 48 = 0.

VA = 8 V.

Leaving currents are −2 A, 2/3 A and 4/3 A. Their sum is zero.

24. One-Unknown-Node Voltage-Source Networks

For an unknown node connected through positive resistors to known potentials:

VAΣ(1/Ri) = Σ(Vi/Ri).

Therefore:

VA = Σ(Vi/Ri)/Σ(1/Ri)

A branch connected to ground has Vi = 0.

One-node network connected to known source potentials

Figure 1.32
The unknown centre node connects through R1 to V1, through R2 to V2 and through Rg to reference.

The result is a conductance-weighted average of the connected known potentials when the network contains only positive resistors at that unknown node.

Consequently, VA lies between the smallest and largest known connected potentials. A current source or another additional element can change this bound, so the condition must be checked before using it.

After finding VA, calculate every requested branch current. A lower-voltage source may receive current while a higher-voltage source delivers current.

Efficient Working

Using kΩ with mA is convenient for small networks. The same equation works in base SI units, but every term must use a consistent scale.

Do not stop at a node potential when the problem asks for branch current or load power.

Worked Problem 1.71: One-Node Network

One-node network for problem 1.71

Figure 1.33
V1 and V2 are known source-node potentials relative to the common bottom reference.

Problem: R1 = 2 Ω to V1 = 12 V, R2 = 3 Ω to V2 = 6 V and Rg = 6 Ω to ground.

VA(1/2 + 1/3 + 1/6) = 12/2 + 6/3.

VA × 1 = 8.

VA = 8 V.

Currents leaving A:

  • Toward 12 V: (8 − 12)/2 = −2 A.
  • Toward 6 V: (8 − 6)/3 = 0.6667 A.
  • Toward ground: 8/6 = 1.3333 A.

Their signed sum is zero.

Worked Problem 1.72: A 10 V and 5 V Network

One-node network for problem 1.72

Figure 1.34
The unknown node is coupled resistively to two known source voltages and reference.

Problem: R1 = 5 Ω to 10 V, R2 = 5 Ω to 5 V and Rg = 10 Ω to ground.

VA(1/5 + 1/5 + 1/10) = 10/5 + 5/5.

0.5VA = 3.

VA = 6 V.

Leaving currents are:

−0.8 A, 0.2 A and 0.6 A.

The current from the 10 V source enters the node and divides between the other paths.

Worked Problem 1.73: A 24 V and 12 V Network

One-node network for problem 1.73

Figure 1.35
Conductance weighting determines the unknown node voltage.

Problem: R1 = 6 Ω to 24 V, R2 = 12 Ω to 12 V and Rg = 12 Ω to ground.

VA(1/6 + 1/12 + 1/12) = 24/6 + 12/12.

VA/3 = 5.

VA = 15 V.

Leaving currents:

  • Toward 24 V: −1.5 A.
  • Toward 12 V: 0.25 A.
  • Toward ground: 1.25 A.

These currents balance exactly before rounding.

Worked Problem 1.74: A Negative Known Potential

One-node network with a negative known source potential

Figure 1.36
Known node potentials can be positive or negative relative to the selected reference.

Problem: R1 = 3 Ω to 12 V, R2 = 6 Ω to −6 V and Rg = 6 Ω to ground.

VA(1/3 + 1/6 + 1/6) = 12/3 + (−6)/6.

(2/3)VA = 3.

VA = 4.5 V.

Leaving currents:

  • To 12 V: (4.5 − 12)/3 = −2.5 A.
  • To −6 V: (4.5 + 6)/6 = 1.75 A.
  • To ground: 4.5/6 = 0.75 A.

−2.5 + 1.75 + 0.75 = 0.

Worked Problem 1.75: A Kilohm One-Node Network

One-node kilohm network for problem 1.75

Figure 1.37
Both branches terminating at zero potential contribute to total node conductance.

Problem: R1 = 1 kΩ to 5 V, R2 = 2 kΩ to 0 V and Rg = 2 kΩ to ground.

Using kΩ and mA:

VA(1 + 1/2 + 1/2) = 5.

2VA = 5.

VA = 2.5 V.

Leaving currents are:

−2.5 mA, 1.25 mA and 1.25 mA.

25. Two-Node Nodal Analysis

When two node potentials are unknown, write one independent KCL equation at each node and solve the pair simultaneously.

A resistor Rm between A and B contributes:

(VA − VB)/Rm

to the all-leaving equation at A and:

(VB − VA)/Rm

to the all-leaving equation at B.

These terms are equal and opposite.

Two unknown nodes joined by a coupling resistor

Figure 1.38
The coupling resistor connects two unknown potentials. It is not a resistor to ground unless one endpoint is actually the reference.

For a ladder with Vs through R1 to A, R2 from A to ground, R3 from A to B and R4 from B to ground:

(VA − Vs)/R1 + VA/R2 + (VA − VB)/R3 = 0

(VB − VA)/R3 + VB/R4 = 0

Solve by substitution, elimination or a clearly specified matrix method.

The B equation can often be rearranged as:

VB = [R4/(R3 + R4)]VA

This also follows from the unloaded divider formed by R3 and R4 relative to node A.

Do Not Stop Early

Node voltages are intermediate quantities when the requested answer is load current or power.

For R4 connected from B to ground:

I4 = VB/R4

P4 = VB²/R4

Use the actual resistor voltage rather than automatically using VA or the source voltage.

Worked Problem 1.76: Two-Node Resistor Ladder

Two-node ladder for problem 1.76

Figure 1.39
R3 links A and B. R4 terminates at reference, so its voltage is VB.

Problem: Vs = 12 V, R1 = 2 Ω, R2 = 6 Ω, R3 = 3 Ω and R4 = 6 Ω.

At A:

(VA − 12)/2 + VA/6 + (VA − VB)/3 = 0.

At B:

(VB − VA)/3 + VB/6 = 0.

The second equation gives:

VB = (6/9)VA = (2/3)VA.

Substitute into the A equation:

[1/2 + 1/6 + 1/9]VA = 6.

VA ≈ 7.7143 V.

VB ≈ 5.1429 V.

Load current:

I4 = 5.1429/6.

I4 ≈ 0.8571 A.

Source current:

Is = (12 − 7.7143)/2.

Is ≈ 2.1429 A.

Worked Problem 1.77: A Scaled Ladder

Two-node ladder for problem 1.77

Figure 1.40
The same node-equation structure applies with different source and resistance values.

Problem: Vs = 24 V, R1 = 4 Ω, R2 = 12 Ω, R3 = 6 Ω and R4 = 12 Ω.

At A:

(VA − 24)/4 + VA/12 + (VA − VB)/6 = 0.

At B:

(VB − VA)/6 + VB/12 = 0.

Therefore:

VB = (12/18)VA = (2/3)VA.

Substitution gives:

[1/4 + 1/12 + 1/18]VA = 6.

VA ≈ 15.4286 V.

VB ≈ 10.2857 V.

I4 = VB/12.

I4 ≈ 0.8571 A.

Source current:

Is ≈ 2.1429 A.

The node voltages double relative to the previous example while the relevant resistance values also double, preserving the currents.

Worked Problem 1.78: Kilohm Ladder

Two-node kilohm ladder for problem 1.78

Figure 1.41
The load voltage is obtained from the second node before calculating its current.

Problem: Vs = 10 V, R1 = 1 kΩ, R2 = 2 kΩ, R3 = 1 kΩ and R4 = 3 kΩ.

Using kΩ:

(VA − 10)/1 + VA/2 + (VA − VB)/1 = 0.

(VB − VA)/1 + VB/3 = 0.

The B equation gives:

VB = (3/4)VA.

Substituting:

[1 + 1/2 + 1/4]VA = 10.

VA ≈ 5.7143 V.

VB ≈ 4.2857 V.

I4 = 4.2857/3.

I4 ≈ 1.42857 mA.

Source current:

Is = (10 − 5.7143)/1.

Is ≈ 4.28571 mA.

Worked Problem 1.79: A Second Two-Node Ladder

Two-node ladder for problem 1.79

Figure 1.42
Node equations preserve the shared-branch voltage difference with opposite signs.

Problem: Vs = 18 V, R1 = 3 Ω, R2 = 6 Ω, R3 = 2 Ω and R4 = 4 Ω.

At A:

(VA − 18)/3 + VA/6 + (VA − VB)/2 = 0.

At B:

(VB − VA)/2 + VB/4 = 0.

Therefore:

VB = (4/6)VA = (2/3)VA.

Substitution gives:

[1/3 + 1/6 + 1/6]VA = 6.

VA = 9 V.

VB = 6 V.

I4 = 6/4.

I4 = 1.5 A.

Source current:

Is = (18 − 9)/3.

Is = 3 A.

The current through R2 is 9/6 = 1.5 A, so source current divides equally between the grounded R2 branch and the R3–R4 path.

26. Nodal Analysis with Current Injection

An ideal current source fixes its branch current in the arrow direction. The surrounding network determines the voltage needed to support that current.

For a source injecting Is into a node connected to grounded resistors R1 and R2:

Is = VA/R1 + VA/R2.

Therefore:

VA = Is(R1 || R2)

Current source injecting current into a resistive node

Figure 1.43
The source injects Is into the upper node. Positive resistor currents flow toward reference when VA is positive.

If the source arrow is reversed, its injection is negative in the same KCL convention.

The node voltage can become negative without violating the passive nature of positive resistors. The actual resistor currents then flow from reference toward the negative node.

An ideal current source develops the voltage required by the mathematical model. Real current sources have compliance limits, but no additional voltage should be invented when only an ideal current is specified.

Power Check

For a positive injection raising the node above ground, the ideal current source delivers power while the grounded resistors absorb it.

The total resistor dissipation should equal the magnitude of source-delivered power.

Worked Problem 1.80: Current-Source Node Voltage

Problem: A source injects 3 A into A. Resistors 6 Ω and 3 Ω connect A to ground.

Rp = 6 || 3.

Rp = 2 Ω.

VA = 3 × 2.

VA = 6 V.

Downward currents:

I1 = 6/6.

I1 = 1 A.

I2 = 6/3.

I2 = 2 A.

The two currents add to the 3 A injection.

Worked Problem 1.81: A Milliampere Injection

Problem: Is = 12 mA, R1 = 1 kΩ and R2 = 2 kΩ.

Rp = (1 × 2)/(1 + 2).

Rp = 0.6666667 kΩ.

VA = 12 mA × 0.6666667 kΩ.

VA = 8 V.

Downward currents:

I1 = 8 mA.

I2 = 4 mA.

Worked Problem 1.82: Negative Injection

Problem: Signed injection is −2 A into A. Both grounded resistors are 4 Ω.

Rp = 4 || 4.

Rp = 2 Ω.

VA = −2 × 2.

VA = −4 V.

Each downward reference current is:

I = −4/4.

I = −1 A.

The physical current in each resistor is 1 A upward from ground toward A.

27. Mesh Analysis and Shared Resistance

Mesh analysis uses KVL with independent mesh-current variables for a planar network.

Assign a direction to each mesh, commonly clockwise.

A resistor belonging only to mesh 1 carries I1. A resistor shared by two clockwise meshes usually carries the difference of the two mesh currents in a chosen branch direction.

If downward through the shared resistor follows mesh 1:

Ishared = I1 − I2

Two clockwise mesh currents sharing a resistor

Figure 1.44
Clockwise mesh references oppose in the centre branch. Its downward current is I1 − I2.

The coefficient multiplying a mesh’s own current is the sum of resistances around that mesh.

A shared resistor contributes a negative coefficient for the neighbouring clockwise mesh current.

The source term depends on traversal through its marked polarity.

After solving, convert mesh variables into actual requested branch currents. Mesh currents are mathematical variables used to reconstruct physical branch currents.

Essential Distinction

A shared resistor does not automatically carry I1 or I2 alone. Equal clockwise mesh currents can produce zero current in their common branch.

Worked Problem 1.83: Shared Branch Current

Problem: I1 = 2 A and I2 = 0.75 A, both clockwise. The shared resistor is 4 Ω, with downward reference following mesh 1.

Ishared = 2 − 0.75.

Ishared = 1.25 A downward.

Vdown = IsharedR.

Vdown = 1.25 × 4.

Vdown = 5 V.

P = 1.25² × 4.

P = 6.25 W.

Using 2² × 4 would overestimate power because 2 A is a mesh variable, not the actual shared-branch current.

28. Two-Mesh Networks with One Source

Consider a left source E rising upward, outer resistors Ra and Rb and shared resistor Rs.

With two clockwise mesh currents:

(Ra + Rs)I1 − RsI2 = E

−RsI1 + (Rb + Rs)I2 = 0

General two-mesh resistor network with one source

Figure 1.45
The left mesh contains E, Ra and Rs. The right mesh contains Rb and Rs without an independent source.

The shared downward current is:

Ishared = I1 − I2

The source branch carries I1. The outer right resistor carries I2 in its assigned mesh direction.

For this one-source circuit, power balance is:

EI1 = RaI1² + RbI2² + Rs(I1 − I2)²

This network can also be solved by reducing Rs parallel to Rb, then adding Ra in series. Reduction provides an independent check on the mesh equations.

Interpretation

A mesh current is a mathematical loop variable. It is not an additional physical current circulating alongside the branch currents.

The branch current is the algebraic sum of mesh contributions that pass through that branch.

Worked Problem 1.84: One-Source Two-Mesh Circuit

Two-mesh circuit for problem 1.84

Figure 1.46
Ra and Rb are outer resistors. Rs is the shared centre branch.

Problem: E = 12 V, Ra = 2 Ω, Rb = 6 Ω and Rs = 3 Ω.

Mesh equations:

5I1 − 3I2 = 12.

−3I1 + 9I2 = 0.

From the second:

I2 = I1/3.

Substitute:

5I1 − I1 = 12.

I1 = 3 A.

I2 = 1 A.

Ishared = 3 − 1.

Ishared = 2 A downward.

Centre-node voltage:

V = 2 × 3.

V = 6 V.

Worked Problem 1.85: A 24 V Mesh Circuit

Two-mesh circuit for problem 1.85

Figure 1.47
The right outer branch is a wire in this one-source network.

Problem: E = 24 V, Ra = 4 Ω, Rb = 8 Ω and Rs = 4 Ω.

8I1 − 4I2 = 24.

−4I1 + 12I2 = 0.

I2 = I1/3.

Substitute:

8I1 − (4/3)I1 = 24.

I1 = 3.6 A.

I2 = 1.2 A.

Ishared = 3.6 − 1.2.

Ishared = 2.4 A.

Centre voltage:

V = 2.4 × 4.

V = 9.6 V.

Worked Problem 1.86: Mesh Currents in Milliamperes

Kilohm two-mesh circuit for problem 1.86

Figure 1.48
The same mesh structure applies when resistances are expressed in kilohms.

Problem: E = 10 V, Ra = 1 kΩ, Rb = 2 kΩ and Rs = 1 kΩ.

Using kΩ and mA:

2I1 − I2 = 10.

−I1 + 3I2 = 0.

I2 = I1/3.

Substitute:

2I1 − I1/3 = 10.

I1 = 6 mA.

I2 = 2 mA.

Ishared = 4 mA.

Centre-node voltage:

V = 4 mA × 1 kΩ.

V = 4 V.

Worked Problem 1.87: A Second One-Source Network

Two-mesh circuit for problem 1.87

Figure 1.49
Shared current is calculated after solving the two mesh variables.

Problem: E = 18 V, Ra = 3 Ω, Rb = 6 Ω and Rs = 6 Ω.

9I1 − 6I2 = 18.

−6I1 + 12I2 = 0.

I2 = I1/2.

Substitute:

9I1 − 3I1 = 18.

I1 = 3 A.

I2 = 1.5 A.

Ishared = 1.5 A.

Centre voltage:

V = 1.5 × 6.

V = 9 V.

29. Two-Source Networks and Negative Mesh Values

A second source changes the right-hand side of the mesh equations according to its polarity.

When both source top terminals are positive, a clockwise traversal through the right source crosses it from positive to negative. Its contribution is a drop.

The equations become:

(Ra + Rs)I1 − RsI2 = E1

−RsI1 + (Rb + Rs)I2 = −E2

Two-mesh network with two top-positive voltage sources

Figure 1.50
Both source top terminals are positive. The right clockwise mesh encounters E2 as a drop.

A negative I2 means actual current in the right outer branch is opposite the assigned clockwise reference.

Compute source power using the actual branch current direction and source polarity. A source can absorb energy in the ideal model.

The centre-node voltage from mesh analysis must agree with a nodal calculation of the same circuit.

Sign Cue

A source is not negative merely because it appears on the right side of a drawing. Its equation sign follows the marked terminals and selected traversal.

Worked Problem 1.88: Two Sources with Explicit Polarity

Two-source mesh circuit for problem 1.88

Figure 1.51
Top-positive sources fix the outer node potentials. Mesh contributions oppose through Rs.

Problem: E1 = 12 V, E2 = 6 V, Ra = 2 Ω, Rb = 3 Ω and Rs = 6 Ω.

Equations:

8I1 − 6I2 = 12.

−6I1 + 9I2 = −6.

From the second:

I2 = (6I1 − 6)/9.

Substitution gives:

8I1 − 6(6I1 − 6)/9 = 12.

I1 = 2 A.

I2 ≈ 0.6667 A.

Shared downward current:

Ishared ≈ 1.3333 A.

Centre potential:

V = 6 × 1.3333.

V = 8 V.

Worked Problem 1.89: A Negative Right Mesh Current

Two-source mesh circuit for problem 1.89

Figure 1.52
A larger right source can reverse the right mesh reference current.

Problem: E1 = 10 V, E2 = 20 V, Ra = 2 Ω, Rb = 4 Ω and Rs = 4 Ω.

6I1 − 4I2 = 10.

−4I1 + 8I2 = −20.

From the second:

I2 = 0.5I1 − 2.5.

Substitute:

6I1 − 4(0.5I1 − 2.5) = 10.

4I1 + 10 = 10.

I1 = 0 A.

I2 = −2.5 A.

Shared current:

Ishared = 0 − (−2.5).

Ishared = 2.5 A downward.

Centre voltage:

V = 2.5 × 4.

V = 10 V.

The left source has nonzero voltage but zero current, so its power is zero in this operating condition.

Worked Problem 1.90: Unequal Sources and Resistors

Two-source mesh circuit for problem 1.90

Figure 1.53
Source polarities remain explicit while the mesh equations are formed.

Problem: E1 = 18 V, E2 = 6 V, Ra = 3 Ω, Rb = 6 Ω and Rs = 3 Ω.

6I1 − 3I2 = 18.

−3I1 + 9I2 = −6.

From the second:

I2 = (3I1 − 6)/9.

Substitute into the first equation.

I1 = 3.2 A.

I2 = 0.4 A.

Ishared = 3.2 − 0.4.

Ishared = 2.8 A.

Centre potential:

V = 2.8 × 3.

V = 8.4 V.

Worked Problem 1.91: Symmetric Two-Source Network

Symmetric two-source mesh circuit

Figure 1.54
Equal outer sources and equal resistors provide a useful symmetry check.

Problem: E1 = E2 = 12 V and Ra = Rb = Rs = 4 Ω.

8I1 − 4I2 = 12.

−4I1 + 8I2 = −12.

Solving:

I1 = 1 A.

I2 = −1 A.

Shared downward current:

Ishared = 1 − (−1).

Ishared = 2 A.

Centre voltage:

V = 2 × 4.

V = 8 V.

Both sources supply current toward the centre node in the physical circuit, while their clockwise mesh references have opposite signs.

30. Choosing and Cross-Checking an Analysis Method

Use direct series and parallel reduction when the topology clearly permits it.

Nodal analysis is often concise when few node potentials are unknown or current injections are specified.

Mesh analysis is often convenient for a planar network containing a small number of loops and voltage sources.

Comparison of reduction, nodal analysis and mesh analysis

Figure 1.55
Reduction, nodal equations and mesh equations describe the same circuit. Correct solutions agree on physical branch quantities.

A short equation set is useful, but correctness depends on maintaining topology and references.

When an examination asks for a particular method, show that method even if another gives a quick private check.

Do not compare a mesh variable directly with a branch current without accounting for shared elements.

KCL, KVL and power balance detect different mistakes. A missing node branch, reversed source polarity, incorrect shared-current expression and lost unit prefix may produce different patterns of failed checks.

Good Presentation

Keep a labelled diagram with the assumptions. Write equations before substituting numbers. Finish with the requested quantity, unit and interpreted direction.

A correct numerical value without a clear terminal pair or current direction may still be an incomplete answer.

Worked Problem 1.92: Reduction Cross-Check of a Mesh Result

Problem: A 12 V source feeds 2 Ω in series with 6 Ω parallel to 3 Ω. Find source current and current through the 3 Ω branch.

Rp = 6 || 3.

Rp = 2 Ω.

Rt = 2 + 2.

Rt = 4 Ω.

Source current:

Is = 12/4 = 3 A.

Parallel voltage:

Vp = 3 × 2 = 6 V.

Current through 3 Ω:

I3 = 6/3 = 2 A.

Current through 6 Ω is 1 A. These agree with the one-source mesh solution.

31. Thevenin’s Theorem and Terminal Equivalence

Thevenin’s theorem replaces an eligible linear two-terminal source network with an ideal voltage source Vth in series with resistance Rth.

A load connected to those terminals receives the same voltage and current as it would in the original network under the stated model.

Thevenin equivalent of a two-terminal source network

Figure 1.56
The source network is replaced by Vth and Rth while the external load remains connected to the same terminals a and b.

The Thevenin voltage is:

Vth = Vopen-circuit = Va − Vb

The Thevenin resistance is the resistance seen looking into the source network after independent sources are deactivated appropriately.

For the simple networks here, sources are independent and resistors are positive linear elements.

Dependent sources in advanced networks must not simply be erased. They require a suitable analysis such as a test-source method.

Thevenin equivalence preserves the external terminal relationship. It does not reproduce every internal branch current, source power or resistor temperature.

Boundary First

Mark terminals a and b and remove only the external load being studied.

Removing an internal network resistor changes the source network and can produce a different equivalent.

Worked Problem 1.93: Use a Supplied Equivalent

Problem: Vth = 12 V and Rth = 3 Ω. A 9 Ω load is connected.

IL = Vth/(Rth + RL).

IL = 12/(3 + 9).

IL = 1 A.

VL = ILRL.

VL = 9 V.

Equivalent internal drop:

VRth = 1 × 3.

VRth = 3 V.

The 9 V load voltage and 3 V internal drop add to the 12 V Thevenin voltage.

32. Finding the Open-Circuit Voltage Vth

Remove the external load while keeping independent sources active.

Calculate voltage between the marked terminals with the stated polarity.

Open circuit means the disconnected load current is zero. It does not mean every current inside the source network is zero.

Open-circuit voltage of a source divider

Figure 1.57
With the external load removed, the original divider still carries current through R1 and R2.

For a source divider viewed from tap to reference:

Vth = VsR2/(R1 + R2)

If a resistor R3 lies between the tap and the open output terminal, it carries zero current at open circuit. Its voltage drop is therefore zero, so it does not alter Vth in that configuration.

A more complex active network may require nodal or mesh analysis to determine open-terminal voltage.

Frequent Mistake

Independent sources remain active when finding Vth.

Source deactivation belongs to the separate Rth calculation. Turning off the source before finding Vth usually removes the very voltage being sought.

Worked Problem 1.94: Open-Circuit Divider Voltage

Problem: Vs = 12 V, R1 = 2000 Ω and R2 = 1000 Ω. Output terminals are the tap and reference.

Internal divider current:

Idivider = 12/(2000 + 1000).

Idivider = 4 mA.

Vth = IdividerR2.

Vth = 0.004 × 1000.

Vth = 4 V.

External current is zero, but internal current is 4 mA.

Worked Problem 1.95: A Low-Resistance Source Divider

Problem: Vs = 18 V, R1 = 3 Ω and R2 = 6 Ω.

Idivider = 18/(3 + 6).

Idivider = 2 A.

Vth = 2 × 6.

Vth = 12 V.

The open external terminals do not interrupt the internal series path through R1 and R2.

Worked Problem 1.96: Equal Divider Resistors

Problem: Vs = 10 V and R1 = R2 = 10 kΩ.

Idivider = 10/20,000.

Idivider = 0.5 mA.

Vth = 0.5 mA × 10 kΩ.

Vth = 5 V.

Equal divider resistors produce half the source voltage at open circuit.

33. Finding Rth and Deactivating Independent Sources

Remove the external load and deactivate independent ideal sources:

  • Replace an ideal voltage source with a short circuit.
  • Replace an ideal current source with an open circuit.

Then calculate resistance looking into the same terminals a and b.

Deactivated divider network for Thevenin resistance

Figure 1.58
Shorting the ideal divider voltage source makes R1 and R2 parallel as seen from the output.

Setting an ideal voltage source to zero volts makes its terminals equipotential, equivalent to an ideal wire.

Setting an ideal current source to zero amperes prevents current through its branch, equivalent to an open.

Any explicitly modelled internal source resistance is a separate element and remains in the circuit.

For finite positive Rth and delivered output current Iout:

Vab = Vth − IoutRth

The terminal-voltage versus output-current slope is:

Slope = −Rth

Connection Check

Redraw the nodes after deactivation. Components that appeared in series in the active source network can become parallel after a voltage source is replaced by a wire.

The load itself must remain removed during the looking-in resistance calculation.

Worked Problem 1.97: Divider Resistance Seen from the Output

Problem: R1 = 2000 Ω, R2 = 1000 Ω and output series resistance R3 = 0 Ω.

Deactivate the ideal voltage source.

R1 and R2 are now parallel:

Rparallel = (2000 × 1000)/(2000 + 1000).

Rparallel = 666.6667 Ω.

Rth = R3 + Rparallel.

Rth = 666.6667 Ω.

Worked Problem 1.98: Include an Output Series Resistor

Problem: R1 = 3 Ω, R2 = 6 Ω and R3 = 2 Ω between the divider tap and output a.

R1 || R2 = (3 × 6)/(3 + 6).

R1 || R2 = 2 Ω.

Rth = R3 + (R1 || R2).

Rth = 2 + 2.

Rth = 4 Ω.

The output series resistor remains inside the source-network boundary and must be included.

Voltage-Divider Loading

Illustration of voltage-divider loading

Illustration
Voltage-divider loading.

A divider ratio assumes a stated load condition. A finite input resistance can change output voltage. Identify the output port and load before using an unloaded ratio.

Thevenin resistance gives a compact way to describe how strongly that port voltage changes with load current.

34. Reconnecting the Load to the Thevenin Equivalent

After finding Vth and Rth, reconnect RL to the equivalent.

IL = Vth/(Rth + RL)

VL = ILRL

PL = IL²RL

Thevenin equivalent supplying an external load

Figure 1.59
The equivalent source and series resistance feed RL. Open-circuit Vth is not generally the loaded voltage.

KVL gives:

Vth = ILRth + VL

A large RL draws little current, making VL close to Vth.

A small RL increases current and internal equivalent drop in the positive-resistance model.

Rth is an equivalent terminal parameter. Its I²Rth is dissipation in the equivalent representation, not automatically the original network’s total internal power.

Keep the Boundary Honest

Use the equivalent for external load behaviour.

Return to the original network when asked for a particular internal resistor current, source current or internal component power.

Worked Problem 1.99: Complete Divider Thevenin Solution

Problem: Vs = 12 V, R1 = 2000 Ω, R2 = 1000 Ω and RL = 1000 Ω.

Vth = 12 × 1000/3000.

Vth = 4 V.

Rth = 2000 || 1000.

Rth = 666.6667 Ω.

IL = 4/(666.6667 + 1000).

IL = 2.4 mA.

VL = 0.0024 × 1000.

VL = 2.4 V.

PL = 0.0024² × 1000.

PL = 0.00576 W = 5.76 mW.

Worked Problem 1.100: A Low-Resistance Load

Problem: Vs = 18 V, R1 = 3 Ω, R2 = 6 Ω and RL = 4 Ω.

Vth = 18 × 6/9.

Vth = 12 V.

Rth = 3 || 6.

Rth = 2 Ω.

IL = 12/(2 + 4).

IL = 2 A.

VL = 2 × 4.

VL = 8 V.

PL = 2² × 4.

PL = 16 W.

Worked Problem 1.101: Equal Divider and Load Values

Problem: Vs = 10 V, R1 = R2 = 10 kΩ and RL = 10 kΩ.

Vth = 5 V.

Rth = 10 kΩ || 10 kΩ.

Rth = 5 kΩ.

IL = 5/(5000 + 10,000).

IL = 0.333333 mA.

VL = 0.333333 mA × 10 kΩ.

VL ≈ 3.3333 V.

PL = IL²RL.

PL ≈ 0.00111111 W = 1.11111 mW.

A Two-Terminal Network Interface

A Thevenin model describes behaviour seen at a defined port. Open-circuit voltage and equivalent resistance have different derivations.

The number of original internal components does not determine the value of Rth. It is the network’s looking-in resistance after the correct source treatment.

35. Load Variation and Extended Thevenin Examples

Once Vth and Rth are known, several loads can be evaluated without re-solving the complete source network.

Keep the equivalent fixed while changing RL. If source values or internal connections change, find a new equivalent.

Linear Thevenin terminal voltage-current characteristic

Figure 1.60
The characteristic has open-circuit intercept Vth and slope −Rth. Different loads select operating points on that relationship.

For a divider followed by output series resistor R3:

Vth = VsR2/(R1 + R2)

Rth = R3 + (R1 || R2)

R3 carries no open-circuit current, so it does not change Vth. It does carry current after load reconnection, so it affects the loaded terminal voltage.

A measured open-circuit voltage and one known loaded condition can determine a linear equivalent:

Rth = (Vth − VL)/IL

This fitted relationship applies within the assumed linear operating range.

Do Not Extrapolate Carelessly

A fitted linear source model does not establish that a real supply remains linear at arbitrary current or outside its protection limits.

The theorem simplifies the chosen model. It does not remove the need to state that model’s valid conditions.

Worked Problem 1.102: Output Series Resistance Changes Rth

Extended Thevenin network for problem 1.102

Figure 1.61
R3 lies between the divider tap and output a, remaining inside the source-network boundary.

Problem: Vs = 12 V, R1 = 2000 Ω, R2 = 1000 Ω, R3 = 1000 Ω and RL = 2000 Ω.

Open-circuit voltage:

Vth = 4 V.

Parallel resistance:

R1 || R2 = 666.6667 Ω.

Rth = 1000 + 666.6667.

Rth = 1666.6667 Ω.

IL = 4/(1666.6667 + 2000).

IL ≈ 1.09091 mA.

VL = IL × 2000.

VL ≈ 2.1818 V.

Worked Problem 1.103: A Second Output Series Resistor

Extended Thevenin network for problem 1.103

Figure 1.62
The output resistor contributes to Rth even though its open-circuit drop is zero.

Problem: Vs = 18 V, R1 = 3 Ω, R2 = 6 Ω, R3 = 2 Ω and RL = 6 Ω.

Vth = 18 × 6/9.

Vth = 12 V.

Rth = 2 + (3 || 6).

Rth = 4 Ω.

IL = 12/(4 + 6).

IL = 1.2 A.

VL = 1.2 × 6.

VL = 7.2 V.

Worked Problem 1.104: Kilohm Extended Network

Extended Thevenin network for problem 1.104

Figure 1.63
The source-network boundary includes the divider and output series resistance.

Problem: Vs = 10 V, R1 = R2 = 10 kΩ, R3 = 1 kΩ and RL = 10 kΩ.

Vth = 5 V.

Rth = 1 kΩ + 5 kΩ.

Rth = 6 kΩ.

IL = 5/(6000 + 10,000).

IL = 0.3125 mA.

VL = 0.3125 mA × 10 kΩ.

VL = 3.125 V.

Worked Problem 1.105: Several Loads on One Equivalent

Problem: Vth = 12 V and Rth = 3 Ω. Compare RL = 3 Ω, 9 Ω and 21 Ω.

For RL = 3 Ω:

IL = 12/(3 + 3) = 2 A.

VL = 6 V.

For RL = 9 Ω:

IL = 12/(3 + 9) = 1 A.

VL = 9 V.

For RL = 21 Ω:

IL = 12/(3 + 21) = 0.5 A.

VL = 10.5 V.

As load resistance increases, current falls and terminal voltage approaches the 12 V open-circuit value.

36. Ideal Meters and Basic Circuit Checking

An ideal voltmeter has infinite input resistance and is connected across the points whose voltage is measured.

An ideal ammeter has zero resistance and is inserted in series with the branch whose current is measured.

Real meters have finite input resistance or burden resistance and can change the circuit.

Voltmeter and ammeter connection principles

Figure 1.64
Voltage measurement spans load terminals. Current measurement lies in the load path.

A finite voltmeter is included as a parallel load. A finite ammeter resistance is included as a series element.

Do not treat an ammeter as a voltmeter. Placing an ideal zero-resistance ammeter across a source creates a short-circuit model.

Resistance measurement in these examples refers to a de-energised isolated network. Other connected parallel paths can cause the measured equivalent resistance to differ from one component’s marked resistance.

Diagnostic Order

Check the reference node, source polarity and measurement terminals before repeating arithmetic.

A correctly solved set of equations can still answer the wrong voltage if the requested terminal pair was misidentified.

Voltage and Current Measurements

Illustration of voltage and current measurement arrangements

Illustration
Voltage and current measurements.

Voltage is measured between points, while current belongs to a branch. Instrument mode, range and connections must correspond to the desired quantity.

Input loading and lead placement can alter the observed result when those effects are part of the model.

Worked Problem 1.106: Finite Voltmeter Loading

Problem: Vs = 12 V, R1 = 2000 Ω and R2 = 1000 Ω. A 1 MΩ voltmeter measures across R2.

Ideal unloaded output:

V0 = 12 × 1000/3000.

V0 = 4 V.

Meter-loaded lower resistance:

Rlower = 1000 || 1,000,000.

Rlower ≈ 999.001 Ω.

Reading:

Vmeter = 12 × 999.001/(2000 + 999.001).

Vmeter ≈ 3.9973 V.

Percentage reduction:

(V0 − Vmeter)/V0 × 100.

Reduction ≈ 0.0666%.

Worked Problem 1.107: Ammeter Burden Resistance

Problem: A 5 V source drives 100 Ω. An ammeter adds 2 Ω in series.

Without meter:

I0 = 5/100.

I0 = 50 mA.

With meter:

Imeter = 5/(100 + 2).

Imeter ≈ 49.0196 mA.

Percentage reduction:

(50 − 49.0196)/50 × 100.

Reduction ≈ 1.9608%.

The meter changes the current it is intended to measure because its resistance becomes part of the branch.

37. Integrated Problems and Examination Strategy

Integrated problems combine several ideas: divider loading, source resistance, energy, method selection and terminal equivalence.

Begin with the circuit topology and define the requested references. Decide whether reduction, nodal analysis, mesh analysis or Thevenin’s theorem is appropriate.

If a particular method is requested, show the required equations even when a shortcut is available.

Complete electrical circuit solution and verification process

Figure 1.65
A complete answer states the model, solves the requested quantity and verifies the circuit.

A Complete Worked-Solution Pattern

State the given data and assumptions. Identify the diagram connections. Write the governing relationship symbolically before substituting values.

Use consistent units and retain useful precision. Interpret a negative result using the assigned arrow or voltage polarity.

Verify KCL, KVL or power balance as appropriate. Report the requested current, voltage, resistance, power or energy with units.

For design questions, recompute the operating result after selecting component values. For finite instruments, include loading or burden effects before predicting the measurement.

For a Thevenin problem, preserve the source-network and load boundary throughout every stage.

Worked Problem 1.108: Design a Nominal Divider

Problem: Obtain unloaded 3 V from ideal 12 V with divider current 1 mA. Find R1 and R2, then examine a 3 kΩ load.

Total resistance:

Rtotal = 12/0.001.

Rtotal = 12 kΩ.

Lower resistor:

R2 = 3/0.001.

R2 = 3 kΩ.

Upper resistor:

R1 = 12 − 3.

R1 = 9 kΩ.

With RL = 3 kΩ:

Rlower = 3 kΩ || 3 kΩ.

Rlower = 1.5 kΩ.

Loaded output:

Vloaded = 12 × 1.5/(9 + 1.5).

Vloaded ≈ 1.7143 V.

The unloaded design meets 3 V, but the specified load substantially lowers its output.

Worked Problem 1.109: Source Power and Energy

Problem: E = 12 V, r = 1 Ω and RL = 5 Ω. The load operates for 10 minutes.

Current:

I = 12/(1 + 5).

I = 2 A.

Load power:

PL = 2² × 5.

PL = 20 W.

Internal heat rate:

Pr = 2² × 1.

Pr = 4 W.

Time:

t = 600 s.

Load energy:

WL = 20 × 600.

WL = 12,000 J.

Internal heat:

Wr = 4 × 600.

Wr = 2400 J.

The ideal EMF supplies 14,400 J, equal to these two energy transfers.

Worked Problem 1.110: Equivalent from Terminal Data

Problem: A linear network has open-circuit voltage 10 V. At a delivered current of 2 A, terminal voltage is 6 V. Find its equivalent and the current for an 8 Ω load.

Vth = 10 V.

Rth = (10 − 6)/2.

Rth = 2 Ω.

For RL = 8 Ω:

IL = 10/(2 + 8).

IL = 1 A.

VL = 1 × 8.

VL = 8 V.

The result uses the assumed linear source characteristic represented by the supplied data.

Worked Problem 1.111: Detect a Wrong Node Equation

Problem: Node A connects through 2 kΩ to +10 V and through 3 kΩ to +4 V. A student writes VA/2 + VA/3 = 0 using kΩ and mA. Correct the equation.

The other endpoints are not ground.

Correct KCL:

(VA − 10)/2 + (VA − 4)/3 = 0

Multiply by 6:

3VA − 30 + 2VA − 8 = 0.

5VA = 38.

VA = 7.6 V.

Leaving currents are:

(7.6 − 10)/2 = −1.2 mA.

(7.6 − 4)/3 = 1.2 mA.

They balance. The incorrect equation falsely treated both known source nodes as zero potential.

Worked Problem 1.112: Original Internal Power Is Not I²Rth

Problem: A 12 V divider has R1 = R2 = 6 Ω. Its external output is open. Find original source-network power and compare with the open-port Thevenin model.

Original divider current:

I = 12/(6 + 6).

I = 1 A.

Total original resistor power:

P = 1² × 12.

P = 12 W.

Equivalent parameters:

Vth = 6 V.

Rth = 3 Ω.

At the open external port:

IL = 0 A.

Equivalent resistor power:

Pth = IL²Rth.

Pth = 0 W.

Both circuits have the same open-terminal voltage and external current. Their internal power differs because Thevenin equivalence preserves terminal behaviour rather than the complete internal energy distribution.

38. Formula Sheet with Conditions

Quantity or Method Relationship Main Condition
Constant-current charge Q = It Current constant over interval
Average current Iavg = ΔQ/Δt Use total charge and total time
Instantaneous current i = dQ/dt Time-varying charge description
Electron count n = Q
Potential difference VAB = VA − VB Common reference
Constant-voltage energy W = VQ Direction and sign interpreted
Ohmic resistor V = IR Constant physical conditions
Conductor resistance R = ρL/A Uniform conductor model
Conductance G = 1/R Positive finite resistor
Series resistance Req = ΣRi Same current
Parallel resistance 1/Req = Σ1/Ri Same two nodes
Two parallel resistors Req = R1R2/(R1 + R2) Two branches
Unloaded divider V2 = VsR2/(R1 + R2) No extra tap current
Loaded divider Replace R2 by R2
Two-branch current divider I1 = ItR2/(R1 + R2) Parallel branch topology
General current divider Ii = ItGi/ΣG Common branch voltage
Resistor power P = VI = I²R = V²/R Matching element quantities
Passive absorbed power p = vi Current enters positive terminal
Constant-power energy W = Pt Power constant
Watt-hour conversion 1 Wh = 3600 J Hours converted to seconds
Practical delivering source V = E − Ir Delivery current convention
KCL ΣI = 0 Consistent current references
KVL ΣV = 0 Complete closed traversal
Node-to-node current IAB = (VA − VB)/R Actual resistor endpoints
Shared mesh branch Ibranch = I1 − I2 Directions as defined
Thevenin load current IL = Vth/(Rth + RL) Same external terminals
Load power PL = IL²RL Actual load current
Linear terminal relation V = Vth − IoutRth Delivered output-current reference

Formula Conditions

A correct formula applied to the wrong topology gives an incorrect answer.

Divider rules depend on loading and actual node connections. Resistor power uses that resistor’s own voltage or current.

Equal wire-node potentials assume ideal conductors. Thevenin equivalence concerns the selected external terminals and does not guarantee identical internal dissipation.

Before using any expression, identify the quantity being calculated, its reference direction, its units and the assumptions behind the equation.

39. Short-Answer Questions with Complete Answers

1. Is Charge Consumed in a Resistor?

Answer: No. Charge continues through the conducting path while electrical energy is converted into heat.

In steady operation, current entering an isolated two-terminal resistor equals current leaving it. The resistor absorbs energy rather than destroying charge.

This distinction explains why the same current flows through every element in an unbranched series circuit. Charge conservation also provides the foundation for Kirchhoff’s Current Law at a junction.

2. Is EMF a Mechanical Force?

Answer: No. EMF is energy supplied per unit charge and is measured in volts.

The word force in its historical name does not make its SI unit the newton.

A practical source’s terminal voltage may fall below its EMF during delivery because current causes an internal drop. EMF describes the ideal energy-per-charge source parameter, while terminal voltage is measured across the external source terminals.

3. What Does a Negative Solved Current Mean?

Answer: It means actual conventional current flows opposite to the chosen positive arrow.

Keep the signed answer in the equations and interpret its direction afterward.

A negative current does not automatically indicate an arithmetic error or an impossible circuit. If IAB = −2 A, the actual current is 2 A from B to A. Reversing the arrow would make its numerical value positive.

4. Can Two Resistors Be in Series if Their Common Junction Has Another Branch?

Answer: Not in the ordinary series-reduction sense when the additional branch carries current.

Series reduction requires the same current through both resistors. A branching current at the junction generally makes those currents different.

Connectivity must be checked rather than judged from the way symbols are drawn. A special open branch may carry zero current under the stated condition, but that condition must be established.

5. Why Is Parallel Equivalent Resistance Smaller Than Either Branch?

Answer: Adding a positive parallel branch adds conductance.

At the same applied voltage, total current increases. Since Req = V/It, the equivalent resistance decreases.

For two positive finite branches, the result is below the smaller branch resistance. This bound is a useful numerical check. A computed parallel equivalent larger than both branches indicates an error in formula use, arithmetic or topology.

6. Why Does Loading Reduce a Divider Output?

Answer: A load across the lower resistor reduces the equivalent resistance of that lower leg.

Under a fixed ideal source, the lower leg then receives a smaller fraction of the applied voltage.

The current through the upper resistor splits between the lower resistor and the external load. Therefore the original unloaded series-divider assumption no longer applies. Replace the lower resistor with its parallel combination with the load.

7. Why Does the Current Divider Use the Opposite Resistance?

Answer: Parallel branches share voltage, so their currents vary inversely with resistance.

For two branches, algebra gives:

I1 = ItR2/(R1 + R2)

The opposite resistance appears because the smaller branch resistance must receive the larger current.

The current-divider result should be checked against this physical relationship and against the requirement that both branch currents add to total current.

8. Can an Ideal Voltage Source Absorb Power?

Answer: Yes. If current enters its positive terminal, its passive-reference power is positive.

Another source can drive energy into it in an ideal circuit model. If current leaves its positive terminal, it delivers power.

The source model alone does not determine the power sign. Current direction and terminal polarity must be considered together. This mathematical statement does not define an acceptable real-battery charging arrangement.

9. What Is the Difference Between Power and Energy?

Answer: Power is the rate of energy transfer, measured in watts.

Energy is the accumulated transfer over time and may be expressed in joules, watt-hours or kilowatt-hours.

For constant power:

W = Pt

A high-power load used briefly can transfer the same energy as a smaller load used for longer. Current, power and energy have different units and should not be substituted for one another.

10. Are Node Voltage and Resistor Voltage Always Identical?

Answer: Only when the resistor’s other terminal is at the reference node.

In general, resistor voltage is the difference between its two endpoint potentials:

Vresistor = VA − VB

Using VA/R for every resistor current falsely assumes that every other endpoint is ground.

This is a common nodal-analysis error, especially when an unknown node is connected to several known nonzero source potentials.

11. Is a Mesh Current Always a Resistor Current?

Answer: An unshared resistor may carry one mesh current directly.

A resistor shared by two meshes carries the algebraic combination of the mesh contributions. For two clockwise references, this is often I1 − I2 in the direction following mesh 1.

The branch direction must be stated. Resistor power uses the physical branch current, not one mesh variable chosen without accounting for the other mesh.

12. Are All Source-Network Currents Zero When Finding Vth?

Answer: No. Removing the external load sets only that load current to zero.

Internal resistor paths can remain complete and continue drawing current from the active sources.

An unloaded divider is a clear example: external current is zero, but its two internal resistors still form a series path across the source. Their current determines the open-circuit tap voltage.

13. Why Is an Independent Voltage Source Shorted for Rth?

Answer: Deactivation sets an ideal independent voltage source to zero volts.

Zero potential difference between its terminals is equivalent to an ideal wire.

An independent current source set to zero amperes is replaced by an open circuit instead. Separately modelled source resistance remains in the network. Dependent sources require a suitable additional method and cannot simply be removed using the independent-source rule.

14. Does Thevenin’s Theorem Reproduce Every Internal Component Power?

Answer: No. The theorem reproduces the terminal voltage-current relationship and therefore the behaviour of the external load.

Original internal branch currents and powers require the original circuit.

The equivalent resistor’s I²Rth is not a universal replacement for all original internal dissipation. An original divider may consume power even with its external output open, while its open-port Thevenin equivalent carries zero current.

15. Can an Open Branch Have Voltage and a Short Carry Current?

Answer: Yes.

An ideal open imposes zero current but can support nonzero voltage.

An ideal short imposes zero voltage but can carry a current determined by the surrounding network.

Zero current and zero voltage are different constraints. Confusing them leads to incorrect conclusions about open terminals, bypassed resistors, ideal meters and source deactivation.

40. Long-Answer Questions with Complete Model Answers

1. Explain Basic Electrical Quantities and Ohm’s Law

Answer:

Electric charge is a property of matter and is measured in coulombs. An electron carries negative elementary charge. A collection of electrons has a positive particle count but negative total signed charge.

Electric current is the rate of charge transfer through a cross-section. Average current is ΔQ/Δt, and constant-current charge transfer is Q = It.

Conventional current follows the direction positive charge would move. In metallic conductors, electron drift is opposite to conventional current.

Potential difference is defined between two points:

VAB = VA − VB

A volt corresponds to a joule per coulomb. The choice of reference node changes numerical node potentials but does not change physical potential differences.

EMF is energy supplied per unit charge by a source. It is measured in volts rather than newtons. A practical source model may include internal resistance, making loaded terminal voltage different from EMF.

Resistance relates voltage and current. For a uniform conductor, R = ρL/A. Resistivity is a material property under specified conditions, while resistance also depends on geometry.

Ohm’s law for a linear resistor under constant physical conditions is:

V = IR

Conductance is its reciprocal:

G = 1/R

When voltage is plotted vertically against current horizontally, the slope is resistance. Reversing the axes gives a slope equal to conductance.

Resistor power is:

P = VI = I²R = V²/R

The actual resistor voltage and current must be used. A negative reference current means actual current flows in the opposite direction; it does not invalidate Ohm’s law.

A complete numerical answer identifies the element, states the relevant relationship, substitutes consistent units and interprets its sign using the original references.

2. Explain Series and Parallel Reduction with Suitable Checks

Answer:

Resistors are in series when the same current must pass through each without dividing at an intermediate junction.

For series resistors, KVL gives:

V = IR1 + IR2 + …

Therefore:

Req = R1 + R2 + …

Individual drops are IRi and add to the applied voltage. A positive series equivalent exceeds each individual resistance.

Parallel resistors share the same two terminal nodes and therefore have the same voltage.

KCL gives:

It = V/R1 + V/R2 + …

Therefore:

1/Req = 1/R1 + 1/R2 + …

For two branches:

Req = R1R2/(R1 + R2)

A positive parallel equivalent is below the smallest branch resistance. Lower resistance draws more current at the common voltage.

In a mixed network, identify a genuine series or parallel group, replace it with its equivalent and redraw. Continue until the source sees a single equivalent resistance.

Then calculate source current and work backward through the reductions to recover individual branch quantities.

For R1 in series with R2 parallel to R3, first find Rp = R2 || R3. Total resistance is R1 + Rp. The parallel group receives ItRp rather than the full source voltage.

Useful checks include:

  • Branch currents sum to total current.
  • Complete-path voltage drops sum to source voltage.
  • Series and parallel equivalent bounds are satisfied.
  • Total resistor power equals ideal-source delivered power.

Visual proximity is not sufficient to establish series or parallel connections. Actual node relationships determine which reductions are valid.

3. Derive Voltage-Divider and Current-Divider Relationships

Answer:

For two unloaded series resistors across Vs, common current is:

I = Vs/(R1 + R2)

Voltage across R2 is:

V2 = IR2.

Substitution gives:

V2 = VsR2/(R1 + R2)

The resistor across which voltage is requested appears in the numerator.

The derivation assumes no additional current leaves the tap. If load RL is connected across R2, replace the lower leg with R2 || RL before applying the divider form.

For a two-branch current divider, both resistors have common voltage V.

I1 = V/R1.

I2 = V/R2.

Total current is:

It = V(1/R1 + 1/R2).

Solving for V and substituting into I1 gives:

I1 = ItR2/(R1 + R2)

Similarly:

I2 = ItR1/(R1 + R2)

The opposite resistance appears because branch current is inversely proportional to its own resistance.

For several parallel branches:

Ii = ItGi/ΣG

where Gi = 1/Ri.

Check that all branch currents add to total current. For positive resistors at a common voltage, the lower resistance receives the larger current.

Voltage division and current division are consequences of topology and Kirchhoff’s laws. They should not be applied before confirming the actual connections and loading assumptions.

4. Explain KCL, KVL and a Reliable Sign Convention

Answer:

Kirchhoff’s Current Law states that the algebraic sum of currents at a node is zero.

It follows from conservation of charge in the steady circuit model. Without net accumulation, total entering current equals total leaving current.

Assign branch arrows before writing the equation. Either take all leaving currents as positive or write entering currents on one side and leaving currents on the other.

Retain signed unknowns. A negative solution means actual current opposes its assigned arrow.

Kirchhoff’s Voltage Law states that the algebraic sum of potential changes around a closed path is zero.

For resistor traversal with its current, the potential change is −IR. Traversal against current gives +IR.

For a source, moving from negative to positive gives +E. Moving from positive to negative gives −E.

The loop may be traversed in either direction, provided every term follows that direction consistently. Reversing traversal reverses all terms and leaves the physical solution unchanged.

For a source E driving series R1 and R2:

E − IR1 − IR2 = 0.

Thus:

I = E/(R1 + R2)

KCL checks current conservation at junctions. KVL checks consistent potential differences around paths.

Power balance provides another useful check:

Σp = 0

The laws do not mean that current or voltage is consumed. Energy is transferred while charge continues through the network.

A reliable solution keeps the original references throughout the algebra and interprets signs only after the equations have been solved.

5. Describe Nodal Analysis and Its Branch-Current Logic

Answer:

Nodal analysis determines node potentials relative to one selected reference node.

Choose a convenient reference and label the other potentials. An ideal voltage source connected directly to reference may fix a node potential immediately.

At each unknown node, apply KCL. Write resistor current from a starting node to an ending node as their potential difference divided by resistance.

For A connected through R1 to V1, through R2 to V2 and through Rg to ground:

(VA − V1)/R1 + (VA − V2)/R2 + VA/Rg = 0

Grouping terms produces:

VA(1/R1 + 1/R2 + 1/Rg) = V1/R1 + V2/R2

For a positive resistor-only connection to known potentials, VA is a conductance-weighted average.

With two unknown nodes, a coupling resistor Rm contributes:

(VA − VB)/Rm

at A and:

(VB − VA)/Rm

at B.

Write one independent equation at each unknown node and solve them simultaneously.

After finding node potentials, calculate the requested branch currents using actual endpoint differences. A resistor joining two nonzero nodes does not have voltage VA alone.

Calculate powers only after the required branch voltage or current has been established.

Check signed KCL residuals and interpret negative potentials relative to the selected ground. A negative node voltage is valid and does not imply a negative resistance.

Nodal analysis is especially convenient when the number of unknown potentials is small or when current sources inject known currents directly into nodes.

6. Describe Two-Mesh Analysis and Shared-Branch Current

Answer:

For a planar resistor network, assign mesh-current variables, commonly clockwise, and apply KVL around each mesh.

An unshared resistor carries the current of its own mesh. A shared resistor receives contributions from both adjacent meshes.

For two clockwise meshes, the contributions oppose in the common branch. If downward follows mesh 1:

Ishared = I1 − I2

For outer resistors Ra and Rb, shared Rs and a left rising source E:

(Ra + Rs)I1 − RsI2 = E

−RsI1 + (Rb + Rs)I2 = 0

The diagonal coefficients contain the total resistance around each mesh. The off-diagonal coefficient is negative shared resistance for these chosen directions.

Solve the pair and convert the mesh variables into requested physical branch currents.

For a second right source with positive upper terminal, clockwise traversal crosses that source as a drop. The right-hand side of the second equation becomes −E2.

A negative mesh current reverses the corresponding reference. It does not require changing the original equation or discarding the result.

For the one-source circuit, verify:

EI1 = RaI1² + RbI2² + Rs(I1 − I2)²

The shared resistor power must use the actual difference current.

Mesh currents are a mathematical representation. They are not additional independent physical currents beyond those in the circuit branches.

A comparison with nodal analysis must therefore compare reconstructed branch quantities rather than unrelated variable names.

7. State and Apply Thevenin’s Theorem

Answer:

Thevenin’s theorem states that an eligible linear two-terminal source network can be replaced externally by an ideal voltage Vth in series with resistance Rth.

The equivalent gives the same terminal voltage and current for the external load under the model assumptions.

First identify terminals a and b and remove the external load. Keep independent sources active and calculate:

Vth = Va − Vb

under open-circuit external loading.

Next deactivate independent sources. Replace ideal voltage sources by shorts and ideal current sources by opens. Keep internal resistors and determine the resistance seen looking into a and b.

For a divider Vs, R1 and R2 viewed from the tap to reference:

Vth = VsR2/(R1 + R2)

Rth = R1 || R2

If output series resistor R3 lies between the tap and terminal a:

Rth = R3 + (R1 || R2)

while Vth remains unchanged at open circuit because R3 carries no current.

Reconnect RL:

IL = Vth/(Rth + RL)

VL = ILRL

PL = IL²RL

Verify a simple result directly in the original network.

Dependent sources cannot simply be removed using the independent-source rule. More advanced networks require a suitable test-source or other analysis.

The equivalent preserves the chosen port relationship. Original internal source currents and component powers require the original circuit.

Thevenin’s theorem is particularly useful when several different loads must be examined while the source network remains fixed.

8. Explain Power Balance and Energy Calculations

Answer:

Under the passive sign convention, absorbed power is:

p = vi

with current entering the labelled positive terminal.

Positive power indicates absorption. Negative power indicates delivery.

A positive resistor absorbs:

P = I²R

An ideal source can deliver or absorb depending on the current direction relative to its terminal polarity.

For a complete ideal DC network:

Σp = 0

Therefore total delivered power equals total absorbed power.

Include all sources and resistors in the chosen boundary. In a practical source model, ideal-EMF delivery divides between external load power and internal heating.

For constant power over a time interval:

W = Pt

Use seconds for joules and hours for watt-hours.

1 Wh = 3600 J

1 kWh = 3.6 × 10⁶ J

For variable operating states, calculate each Pi ti and add the results. An average-power calculation must use total energy divided by total elapsed time.

For example, 100 W used for two hours transfers 200 Wh or 0.2 kWh.

Under a supplied hypothetical tariff of 8 currency units per kWh, the energy charge is:

0.2 × 8 = 1.6 currency units.

Other charges are added only when specified.

Do not confuse ampere-hours with watt-hours. Ah measures charge transfer. Energy also depends on voltage.

A complete answer states the operating model, time unit, circuit boundary and interpretation of absorbed or delivered energy.

41. Final Revision and Answer Checklist

Check the Physical Meaning

Current is charge transferred per unit time. Voltage is potential difference between points. EMF is energy supplied per charge.

Resistance does not consume current. A resistor absorbs energy while the same steady charge rate enters and leaves.

Power and energy are different quantities. A watt is an energy-transfer rate, while joules and watt-hours describe accumulated energy.

Use a component’s actual voltage and current in its power calculation.

Check the Circuit Topology

Series means the same current must flow through the elements.

Parallel means both terminals are connected to the same two nodes.

A loaded divider differs from an unloaded divider because current leaves the tap.

An ideal open imposes zero current. An ideal short imposes zero voltage.

Mark nodes before combining components. The appearance of a drawing cannot replace a connectivity check.

Check the Analysis Method

KCL uses signed branch currents.

KVL uses signed potential changes around a complete loop.

Nodal currents use endpoint voltage differences.

Mesh shared-branch current uses the correct algebraic combination of mesh variables.

Thevenin sources remain active for Vth. Independent source deactivation belongs to Rth.

The external load boundary must remain unchanged throughout a Thevenin calculation.

Final Test What Should Agree
Units Both sides of every equation have matching dimensions
KCL Entering and leaving currents balance
KVL Complete-loop potential changes sum to zero
Series resistance Positive equivalent exceeds each component
Parallel resistance Positive equivalent is below the smallest branch
Resistor power Nonnegative for positive resistance
Total power Delivered power equals absorbed power
Divider loading Loaded output uses the actual parallel lower leg
Mesh conversion Physical shared current includes both mesh contributions
Thevenin verification Original and equivalent load results agree
Measurement model Meter loading or burden is included when specified
Energy Time units match the stated energy unit

Final Memory Line

Label the circuit, write the governing equation, substitute consistent units, solve, interpret the sign and verify the result.

A numerical answer is complete when it identifies the intended terminals or branch, gives the correct unit and explains any negative reference result.

←
Previous Story

Calculus and Linear Algebra Unit 5 Notes- AKTU B.Tech 1st Year

Next Story

Fundamentals Of Electrical Engineering Unit 2 Notes- AKTU B.Tech 1st Year

→

Leave a Reply

Your email address will not be published. Required fields are marked *

NotesGallery Assistant

Chatbot

Schedule Appointment

Fill out the form below, and we will be in touch shortly.
Contact Information
Vehicle Information
Preferred Date and Time Selection